Controller defaults – GE Industrial Solutions CPS6000-M2 User Manual
Page 79

CPS6000-M2 Installation Guide H5694720
Issue 8 January 2008
79
Controller Defaults
Dip Switch Settings
The Millennium II has 8 dip switch (SW202) positions that may be configured. SW202 is located
on the MCR1 board, above the MCR2 board.
Millennium II Controller Dip Switch Settings
Switch
Position
Default
Description
Closed
(1)
Open
(0)
SW202-8
1
Front Panel Configuration
ENABLED
DISABLED
SW202-7
1 Modem/Aux/Local/Network/
Port
Setting Configuration
(Remote Access)
ENABLED DISABLED
SW202-6
0
Enhanced Security Mode (See Table
5-I, for features affected
ENABLED DISABLED
SW202-5
1
Auxiliary Port Configuration
RS-232
RS-485
SW202-4
0
Remote Rectifier in Standby
ENABLED
DISABLED
SW202-3
0 Boost
Mode
ENABLED
DISABLED
SW202-2
1
Reserved for Future Use
ENABLED
DISABLED
SW202-1
1
Reserved for Future Use
ENABLED
DISABLED
Modem/Aux/Local/Network/ Port Setting Configuration (Remote Access)
The modem and auxiliary ports can be configured for full access or read-only access by properly
configuring DIP switch 202-7. Full access with Read/Write capability is achieved by closing
SW202-7 (Set to a “1”).
Enhanced Security Mode
Restricted access is also available. When Enabled, the controller prevents remote configuration
changes via the modem, network, and auxiliary ports that will affect the state of the plant, even
when logged in as a Super-User or Administrator. This enhanced remote security is enabled and
disabled with DIP switch SW202-6. The functions and parameters restricted with the enhanced
remote security feature are listed below.