GE Industrial Solutions CPS6000-M2 User Manual
Page 66

CPS6000-M2 Installation Guide H5694720
Issue 8 January 2008
66
Millennium II Controller Status and Alarms
Alarm Status LEDs
Status
Function
Condition
Normal
Normal operation, no alarms, inputs and outputs are in
their normal range.
Critical Alarm Power to load equipment is at immediate and high risk.
Major Alarm
Power to load equipment is at immediate risk.
Minor Alarm
A problem requiring attention exists, but power to load
equipment is not at immediate risk.
Battery on
Discharge
Batteries are discharging and delivering current to the
load.
Remote
Access
[LAN/Modem]
Blinks to indicate traffic on an attached LAN or
Modem.
Note: Which conditions are indicated as Critical, Major, and Minor Alarms may be configured by
the user.
Equipment Status LEDs
Status
Function
Condition
AC System
AC input to one or more rectifiers is out of range.
Battery
The batteries are not in a normal operating state.
Controller
The system controller has detected an internal
problem.
Rectifier/Converter
A rectifier or converter power unit in the system has
failed
Distribution
The output distribution is not in a normal operating
state.
Remote Modules
There is a problem with a Remote Peripheral
Module (RPM)
Remote Access
[LAN/Modem]
Blinks to indicate traffic on an attached LAN or
Modem.
Audible Alarm
The controller assembly is equipped with a user configurable alarm
buzzer.
Voltage Test Jacks
Voltage Test Jacks allow you to measure the main plant output voltage
with a hand-held meter.