GE Industrial Solutions CPS6000-M2 User Manual
Page 77

CPS6000-M2 Installation Guide H5694720
Issue 8 January 2008
77
Step
Configuration
Attribute to Change
Menu Path/Action
the cursor to the field and use the <+> or <-> key to Enable or
Disable. Press
High Temp
Comp
This feature allows the system to compensate for high
temperatures.
Volt Step
Down
Battery step temperature can be set from 113-185F. At this
temperature, the system voltage is reduced by 0.17 X # of
cells/string.
High Comp
Limit
This sets the maximum temperature for which thermal
compensation is active.
Decrease
This sets the slope (mV/degC) for high temperature
compensation.
Nominal
Temp
This field set the temperature at which no compensation is
required. The system voltage is at the set-point float mode.
Low Temp Comp
This feature allows the system to compensate for low
temperatures.
Low T Comp
This enables or disables the low temperature compensation
feature.
Low Comp
Limit
This sets the minimum temperature for which thermal
compensation is active.
Increase
This sets the slope (mV/degC) for low temperature
compensation.
Recharge Current
Limit
This feature sets the total amount of current that will be
allowed to recharge the batteries.
Limit
The configuration of this field enables or disables the feature.
8
Limit to
This programmable value sets the maximum amount of
recharge current (in Amps) that will be allowed for recharging
the batteries. The range is from 10 – 1000A.
Contactors
Up to three optional LVD devices can be connected to a
Millennium and configured from this screen.
Contactor 1-3
9
Type
This setting identifies the type of contactor, BATTERY,
LOAD or NONE that has been installed in the plant. Be sure
that the wiring for the contactor being configured matches the