ISGS Settings Worksheet for
Date:
Set A
Siemens Energy & Automation, Inc.
S-9
3400 Value Supervision
3401 Voltage Balance Function
Enabled
Disabled
3402 Voltage Balance Pickup
100 V
Range: 40-120 V (0.1 V steps)
V
3404 Voltage Balance Factor
0.80
Range: 0.58-0.95
(0.01 teps)
3411 Current Sum Function
Enabled
Disabled
3412 Current Sum Pickup
5 A CT 0.5 A
Range: 0.5-5 A (0.1 A steps)
A
1 A CT 0.1 A
Range: 0.1-1 A (0.1 A steps)
A
3414 Current Sum Factor
0.10
Range: 0.10-0.95
(0.01 steps)
3411 Current Balance Function
Enabled
Disabled
3412 Current Balance Pickup 5 A CT 2.5 A
Range: 0.5-5 A (0.1 A steps)
A
1 A CT 0.1 A
Range: 0.1-1 A (0.1 A steps)
A
3414 Current Balance Factor
0.80
Range: 0.10-0.95
(0.01 steps)
3500 Breaker Operation
3501 Interrupted Current Function
Enabled
Disabled
3502 Interrupted Current Pickup
1000.00 kA
Range: 0-9999.9 kA
(1 kA steps)
kA
3503 Breaker Operations Functions
Enabled
Disabled
3504 Breaker Operations Counter
100
Range: 0-65535