ISGS Settings Worksheet for

Date:

Set A

Siemens Energy & Automation, Inc.

S-9

3400 Value Supervision

3401 Voltage Balance Function

Enabled

Disabled

3402 Voltage Balance Pickup

100 V

Range: 40-120 V (0.1 V steps)

V

3404 Voltage Balance Factor

0.80

Range: 0.58-0.95

(0.01 teps)

3411 Current Sum Function

Enabled

Disabled

3412 Current Sum Pickup

5 A CT 0.5 A

Range: 0.5-5 A (0.1 A steps)

A

1 A CT 0.1 A

Range: 0.1-1 A (0.1 A steps)

A

3414 Current Sum Factor

0.10

Range: 0.10-0.95

(0.01 steps)

3411 Current Balance Function

Enabled

Disabled

3412 Current Balance Pickup 5 A CT 2.5 A

Range: 0.5-5 A (0.1 A steps)

A

1 A CT 0.1 A

Range: 0.1-1 A (0.1 A steps)

A

3414 Current Balance Factor

0.80

Range: 0.10-0.95

(0.01 steps)

3500 Breaker Operation

3501 Interrupted Current Function

Enabled

Disabled

3502 Interrupted Current Pickup

1000.00 kA

Range: 0-9999.9 kA

(1 kA steps)

kA

3503 Breaker Operations Functions

Enabled

Disabled

3504 Breaker Operations Counter

100

Range: 0-65535

S