Siemens Energy & Automation, Inc.

27

The Undervoltage function can be enabled or disabled

(2301).

The Curve parameter (2302) allows the selection of a definite

time delay or a characteristic curve. When the definite time

characteristic is selected, the time delay begins as soon as

the device goes into pickup. The inverse time characteristic

utilizes a moderate inverse curve using the time dial.

The Pickup Source Voltage parameter (2303) indicates the

VT connection. If the VTs are connected line-to-ground, the

device can pickup on line-to-line or line-to-ground voltages.

If the VTs are connected line-to-line, the VTs can only pickup

on line-to-line voltages. The maximum continuous voltage

across a VT input is 150 VAC.

The pickup value (2304) is in secondary volts ranging from

60 to 250 V. The function begins timing when any individual

phase voltage exceeds the pickup voltage setting.

The time delay (2305) represents the time between pickup

and trip and can be set when definite time is selected. The

delay can be adjusted from 0.1 to 60.0 seconds in steps of

0.01 second. If the function remains in pickup for longer than

the time delay, the function causes a trip. The delay can also

be set to infinity so that the function never times out.

The Time Dial parameter (2306) is used for the characteristic

curve. The dial allows the time-to-trip of the curve to be

raised or lowered. It can be adjusted from 0.1 to 9.9 in steps

of 0.1.

Each of the two waveform capture buffers (2310 and 2311)

can be independently programmed to freeze snapshots on

pickup or trip.

The function is able to actuate any binary output contact on

pickup, and any trip or binary output contact on trip.

5.13 Phase Sequence Voltage (47)

The Phase Sequence Voltage function operates instanta-

neously if the correct system voltage phase sequence

defined in the hardware configuration is not present at the

device voltage inputs. This function will not respond if the

input to the device is less than 40 V line-to-line or 23.1 V line-

to-neutral. The function operates without delay or inverse

time characteristic. It responds in 100 ms or less.

The Phase Sequence Voltage function can be used to pre-

vent closure of a breaker. The assigned output contact would

be wired to open a contact in the breaker-close circuit and

remain activated until the line rotation is normal.

A2400 Phase Sequence Protection (47)

Address Parameter

Option

2401 Function

Enabled or Disabled

2410 Freeze Wfm 1

on Trip, or None

2411 Freeze Wfm 2

on Trip, or None

The 47 Phase Sequence Voltage function can be enabled or

disabled (2401).

Each of the two waveform capture buffers (2410 and 2411)

can be independently programmed to freeze snapshots on

trip.

The function is able to actuate any binary output contact on

pickup, and any trip or binary output contact on trip.

5.14 Negative Sequence Voltage (47N)

The Negative Sequence Voltage function operates when the

percent negative sequence voltage exceeds the preset value

for a specified time. This function resets instantaneously

when the negative sequence voltage drops below pickup.

The Negative Sequence Voltage function can be enabled or

disabled (2451).

The Curve parameter (2452) allows the selection of a definite

time delay or an inverse curve. The inverse time characteris-

tic utilizes a moderate inverse curve using the time dial.

The pickup value (2453) ranges from 4% to 40% of negative

sequence voltage. The function begins timing when the per-

cent of negative sequence voltage exceeds the preset value

for a specified time.

The time delay (2454) represents the time between pickup

and trip and can be set when definite time is selected. The

delay can be adjusted from 0 to 100 seconds in steps of

0.01 second. The delay can also be set to infinity so that the

function never times out.

The Time Dial parameter (2455) is used for the characteristic

curve. The dial allows the time-to-trip of the curve to be

raised or lowered. It can be adjusted from 0.1 to 9.9 in steps

of 0.1.

A2400 Negative Sequence Voltage (47N)

Address Parameter

Option

2451 Function

Enabled or Disabled

2452 Curve

Definite or Inverse

2453 Pickup 4-40%

negative

sequence

(1% steps)

2454 Time Delay (Def.)

0-100 s (0.01 s steps),

or infinity

2455 Time Dial (Inverse)

0.1-9.9 (0.1 steps)

2456 Max Time (Inverse)

1-250 s (1 s steps)

2457 Blocked at

40-120 V (1 V steps)

2460 Freeze Wfm 2

on Pickup, on Trip, or None

2461 Freeze Wfm 2

on Pickup, on Trip, or None

5