beautypg.com

Protective function configuration – Siemens ISGS SG8158-00 User Manual

Page 31

background image

Protective Function Configuration

Siemens Energy & Automation, Inc.

25

The Directional Phase Time Overcurrent function can be

enabled or disabled (1901).

The Curve parameter (1902) allows the selection of the pre-

programmed characteristic curve used by this function. The

ISGS relay comes with nine standard overcurrent character-

istic curves that can be adjusted with the Time Dial parame-

ter. The custom curve is a user-definable protective curve

that integrates with instantaneous reset. The lower limit of

the custom curve is 1.10. The maximum time to trip is the

time at 1.10.

The range of the pickup value (1903) depends on the sec-

ondary phase CT rating (1 A or 5 A) and the value is in sec-

ondary amperes. The function begins timing when any

individual phase current exceeds the pickup current setting.

The Time Dial parameter (1905) used for the selected curve

allows the time-to-trip of the curve to be raised or lowered

The dial can be adjusted from 0.1 to 9.9 in steps of 0.1.

The Filter parameter (1906) sets the sensing method used by

the function in its pickup calculations. The rms filter uses fun-

damental current plus harmonics, while the fundamental filter

ignores harmonics.

Impedance (1907) sets the angle used by this function.

Impedance determines the direction of current flow being

measured and can be set from 0 to 90 degrees. The direc-

tional characteristic (line) in the complex impedance plane is

shown in Figure 5.2. The directional characteristic is always

perpendicular to the line impedance vector.

The sensing direction (1908) can be set to forward or

reverse. The forward setting allows the directional protection

element to pickup on fault current only in the direction oppo-

site to normal power flow.

Figure 5.2 Directional Characteristic

Each of the two waveform capture buffers (1910 and 1911)

can be independently programmed to freeze snapshots on

pickup or trip.

The function is able to actuate any binary output contact on

pickup, and any trip or binary output contact on trip.

5.10 Directional Neutral or Ground Time

Overcurrent (67N)

The Directional Neutral or Ground Time Overcurrent function

uses a selected time overcurrent characteristic curve to

determine the trip time for the applied current at the fourth

current input, utilizing the voltages present on the VTs to

determine current direction. The defined characteristic

curves are valid over a range of multiple of pickup values.

The function also includes a customer defined curve. Refer

to Appendix A for detailed trip curve information. This func-

tion is only available if the voltage input option is installed.

The Directional Neutral or Ground Time Overcurrent function

can be enabled or disabled (2001).

The Curve parameter (2002) allows the selection of the pre-

programmed characteristic curve used by this function. The

ISGS relay comes with nine standard overcurrent character-

istic curves that can be adjusted with the time dial parameter

(see below). The custom curve is a user-definable protective

curve that integrates with instantaneous reset. The lower limit

of the custom curve is 1.10. The maximum time to trip is the

time at 1.10.

A2000 Directional Neutral or Ground Time Overcurrent

(67N)

Address Parameter

Option

2001 Function

Enabled or Disabled

2002 Curve

Inverse

Short Inverse

Long Inverse

Moderately Inverse

Custom

Very Inverse

Extremely Inverse

Definite Inverse

Slightly Inverse

I

2

T Without Limit

2003 Pickup

5 A CTs: 0.5-20 A or

1 A CTs: 0.1-4 A

(0.1 A steps)

2005 Time Dial

0.1-9.9 (0.1 steps)

2006 Filter

rms or fundamental

2007 Impedance

0-90°

2008 Direction

Forward or Reverse

2010 Freeze Wfm1

on Pickup, on Trip, or None

2011 Freeze Wfm2

on Pickup, on Trip, or None

5

isv3o_1.bk : isv3opro.frm Page 25 Wednesday, August 7, 1996 10:51 AM