beautypg.com

Control & communications – Siemens ISGS SG8158-00 User Manual

Page 46

background image

Control & Communications

40

Siemens Energy & Automation, Inc.

and, therefore, apply to both sets. Examples are protective

function enable settings and matrixed output contacts such

as waveform buffers and blocking. All parameter set func-

tions require a password.

6.11.1 Active Set

The active parameter set refers to the parameter set that is

currently used by the ISGS relay—set A or set B. The Active

Set parameter (7101) indicates which set is currently active

on the LCD using the letter A or B.

Refer to Section 6.11.3 on how to make a parameter set the

active set.

6.11.2 Default Set

The default set refers to factory default parameter settings.

These are stored in read-only memory (ROM) and cannot be

overwritten. The default set cannot become an active set in

itself, it has to be copied to either set A or set B (7104 and

7105).

6.11.3 Switching Sets

A parameter set can be made active by selecting the desired

set in the Activation parameter (7103). Switching between

sets requires 4.5 seconds.

Note: Switching the parameter sets could cause a

trip if the pickups are set lower than in the

previous set. View the settings before acti-

vating the new set.

Switching between parameter sets for viewing and configur-

ing parameter settings is possible regardless of address or

address level currently displayed by the LCD, or whether the

parameter can be configured to an alternate setting.

1. At any address, press the F key

followed by either 1 (set A) or 2 (set B).

The LCD displays the following message:

A1502 Pickup 50
110 A

A1502FPickup 50
110 A

PARAMETER SET
COPIED TO EDIT

2. Press Enter. The parameter set has switched to the

alternate set. The LCD displays the same address and

function as before the switch, but the address prefix has

changed to the letter representing the displayed param-

eter set. The alternate parameter may or may not con-

tain a value depending on whether the alternate

parameter had been configured before.

If the parameter was not configurable to an alternate set

(had no prefix), the display will not have changed.

Note: Switching the parameter sets for viewing

and configuration does not make the alter-

nate set active.

For detailed descriptions on how to display, configure, save,

and switch parameters, and when to use a password, refer

to the standard operating procedures in Section 3.5.

Exceptions to the switching of sets are binary inputs, binary

outputs, and the trip contacts in the 6000 address blocks.

For these parameter settings, the relay retains these values

regardless of the parameter set. For example, if the output

contact is set while set A is active, switching to set B will not

change the output contact setting.

6.11.4 Copying Sets

Parameter settings for set A can be copied to set B and vice

versa (7106 and 7107). Factory default settings can also be

copied to either set A or set B (7104 and 7105), but no

parameter set can override the default settings.

B1502 Pickup 50

6

isv3o_1.bk : isv3oc&c.frm Page 40 Wednesday, August 7, 1996 10:51 AM