beautypg.com

Control & communications – Siemens ISGS SG8158-00 User Manual

Page 43

background image

Control & Communications

Siemens Energy & Automation, Inc.

37

Binary Outputs (7409) displays the output contact status as

illustrated in Figure 6.3. The status updates automatically as

they change.

Figure 6.3 Output Contact Status

6.10 Self-Monitoring (Value Supervision)

Value supervision refers to the relay’s ability to monitor its

own input and measurement functions for problems. The

complete chain, from input transformers up to and including

the A/D converter internal to the ISGS, is monitored by a

plausibility check on the measured values. These checks

consist of voltage balance checks, current balance checks,

and current summation checks.

Voltage or current balance checks can be performed to

detect open or short circuits in the external transformers and

their connections. Current summation checks are performed

on the instantaneous samples of the A/D converter.

A useful application of the current and voltage balance and

monitoring functions is the detection of blown VT fuses. A

blown fuse condition can be said to exist when the following

conditions are present:

Voltage is present but unbalanced,

AND

current is present but NOT unbalanced.

Therefore, a voltage balance alarm in the absence of a cur-

rent unbalance alarm is a good indication that a fuse is

blown. If a current unbalance alarm were also active, it would

indicate the presence of negative sequence current and

therefore a fault rather than a blown VT fuse.

Voltage Balance

The Voltage Balance function can be enabled or disabled

(3401). When enabled, the function monitors the phase volt-

ages to see if they are approximately balanced (of equal

magnitude). Balance is defined as the ratio of minimum to

maximum voltage, where the maximum voltage is the largest

and the minimum voltage the smallest of the three voltages

determined by the way the relay is connected (line-to-line or

line-to-neutral).

3400 Value Supervision

Address Parameter

Selection

3401 Function V Bal

Enabled or Disabled

3402 Pickup V Bal

40-120 V (0.1 V steps)

(default is 100)

3404 Factor V Bal

0.58-0.95 (0.01 steps)

(default is 0.8)

3411 Function I Sum

Enabled or Disabled

3412 Pickup I Sum

5 A CTs: 0.5-5 A

1 A CTs: 0.1-1 A

(0.1 A steps)

3414 Factor I Sum

0.10-0.95 (0.01 steps)

(default is 0.1)

3421 Function I Bal

Enabled or Disabled

3422 Pickup I Bal

5 A CTs: 0.5-5 A

1 A CTs: 0.1-1 A

(0.1 A steps)

3424 Factor I Bal

0.10-0.95 (0.01 steps)

(default is 0.8)

V1 25 V

>

AND V2

0.33 V1

AND I2 0.167 I1

<

OR I1 0.1 IN

<

<

where V1 = positive sequence voltage

I2 = negative sequence current

I1 = positive sequence current
IN = nominal current (1 or 5 A)

6

isv3o_1.bk : isv3oc&c.frm Page 37 Wednesday, August 7, 1996 10:51 AM