Introduction

4

Siemens Energy & Automation, Inc.

1.5 Technical Specifications

Applicable Standards

ANSI / IEEE C37.90-1989

IEEE Standard Relays and Relay

Systems Associated With Elec-

tric Power Apparatus

IEC 255-4

Single Input Energizing Quantity

Measuring Relays With Depen-

dent or Independent Time

General Technical Data

Operating ambient temperature

-20°C to +55°C (-4°F to +131°F)

Storage temperature

-40°Cto+75°C (-40°F to+167°F)

Relative humidity

The average relative humidity

may be up to 55% outside of

enclosure for temperatures up to

40°C, with excursions up to

95% for a maximum of 96

hours, without condensation.

Altitude

< 1500 meters

Frequency

50 Hz or 60 Hz, software select-

able

Power Supply AC/DC

DC Rated voltages

48 V (19-56 V),

125 V (46-144 V),

250 V (92-288 V)

Permissible ripple

<10%

AC Rated voltage

120 V rms (102-132 V, 50-60 Hz)

Power consumption

<15W

Input Circuit Ratings

Rated current (In)

1 or 5 A, independently for

phase and ground inputs

Maximum input current

4 x In continuous
10 x In for 10 s
100 x In for 1 s

CT burden

<0.1 VA for 1A CT
<0.5 VA for 5A CT

Rated voltage (Vn)

115 or 120 volts

Maximum input voltage

for measurement: 1.25 x Vn

MOV protected at: 2.5 x Vn

VT burden

150k

Trip Circuit

Tripping relays

2 or 3

Contact configuration

(Trip 1, Trip 2, Trip 3)

Contact rating

IEEE/ANSI C37.90-1989, Sec-

tion 6.7 (Make and carry 30 A for

at least 2000 duty cycles, resis-

tive load, interrupted by indepen-

dent means. Duty cycle:

200 ms on, 15 s off, 250 V)

Trip Circuit (continued)

Binary output contacts

(BO1 and BO2)

2 x N.O. (independent,

not rated for tripping)

Maximum switching voltage

300 VDC, 250 VAC

Maximum switching current

8 A

Maximum switching capac-

ity (for currents not inter-

rupted by independent

means)

DC: voltage dependent;

50 W at V

70 VDC

100 W at 48 VDC

270 W at 35 VDC

AC: 2000 VA

Trip source monitor

215 mA for 48 VDC supply

63 mA for 125 VDC supply

36 mA for 250 VDC supply

Source quality checked approxi-

mately every 4 minutes

Isolation

Applicable standards

ANSI/IEEE C37.90-1989,

IEC 255-4, IEC 255-5

Between all circuits (except

communications interfaces, ana-

log inputs and outputs) and

ground, and between these cir-

cuits.

2 kV rms, 50/60 Hz, 1 minute

Between communications inter-

faces, analog inputs and outputs

and ground, and between these

circuits

500 VDC, 1 minute

Across open contacts rated for

tripping

1500 V rms, 50/60 Hz, 1 minute

Across open contacts not rated

for tripping

1000 V rms, 50/60 Hz, 1 minute

Impulse

Applicable standards

IEC 255-4, IEC 255-5

For all circuits (except communi-

cations interfaces, analog

inputs and outputs), transverse

and common mode

class 3, 5 kV, 1.2/50

µ

s, 0.5 J

RS-485 and local communica-

tions interfaces, analog I/Os

class 1, 0 kV

Electrostatic Discharge

Applicable standards

IEC 801-2 (test without cover)

Contact discharge

class 3, 6 kV

Air discharge

class 3, 8 kV

Surge Withstand Capability

Applicable standards

ANSI/IEEE C37.90-1989,

IEC 255-4, IEC 255-22-1,

IEC 41B (CO) 53

For all circuits except communi-

cations interfaces, analog

inputs and outputs

ANSI: Oscillatory and Fast Tran-

sient, transverse and common

mode

IEC: Class 3, 2.5 kV

For RS-485 interface, analog

inputs and outputs

IEC: Class 1, 0.5 kV

Electromagnetic Field

Applicable standards

ANSI/IEEE C37.90.2

All six faces

10 V/m (+100%, -0%),

2-1000 MHz

1