ISGS Settings Worksheet for
Date:
Set B
Siemens Energy & Automation, Inc.
S-21
B2200 Overvoltage (59)
B2201 Function 59
Enabled
Disabled
B2202 Curve 59
Inverse
Moderately
Inverse
Very Inverse
Definite Inverse
B2203 Pickup Source Voltage 59
(if VT mode is (L-N)
Line-to-Line Line-to-Neutral
B2204 Pickup 59
130 V
Range: 60-250 V (0.1 V steps)
V
B2205 Time Delay 59 (Definite)
0.10 s
Range: 0-60 s (0.01 s steps),
or
∞
s
B2206 Time Dial 59 (Inverse)
0.1
Range: 0.1-9.9 (0.1steps)
2210 Freeze Waveform 1 59
Settings displayed or changed here apply to both parameter sets
2211 Freeze Waveform 2 59
Settings displayed or changed here apply to both parameter sets
B2300 Undervoltage (27)
B2301 Function 27
Enabled
Disabled
B2302 Curve 27
Inverse
Moderately
Inverse
Very Inverse
Definite Inverse
B2303 PU Source V 27
(if VT mode is (L-N)
Line-to-Line Line-to-Neutral
B2304 Pickup 27
50.0 V
Range: 40-230 V (0.1 V steps)
V
B2305 Time Delay 27 (Definite)
0.10 s
Range: 0-60 s (0.01 s steps),
or
∞
s
B2306 Time Dial 27 (Inverse)
0.1
Range: 0.1-9.9 (0.1 steps)
2310 Freeze Waveform 1 27
Settings displayed or changed here apply to both parameter sets
2311 Freeze Waveform 2 27
Settings displayed or changed here apply to both parameter sets
S