ISGS Settings Worksheet for

Date:

Set A

Siemens Energy & Automation, Inc.

S-7

A2500 Overfrequency (81O)

Underfrequency (81U)

A2501 Function 81O

Enabled

Disabled

A2502 Pickup 81O

62.0 Hz

Range: 60.1-65.0 Hz

(0.1 Hz steps)

Hz

A2504 Time Delay 81O

0.10 s

Range: 0-100 s (0.01 s steps),

or

s

2506 Block 81O

40 V

Range: 40-120 V (1 V steps)

V

2510 Frz. Wfm1 81O

on Pickup

on Trip

None

2511 Frz. Wfm2 81O

on Pickup

on Trip

None

A2551 Function 81U

Enabled

Disabled

A2553 Pickup 81U

58.0 Hz

Range: 55.0-59.9 Hz

(0.1 Hz steps)

Hz

A2554 Delay 81U

0.10 s

Range: 0-100 s (0.01 s steps),

or

s

A2556 Block 81U

40 V

Range: 40-120 V (1 V steps)

V

2560 Freeze Waveform 1 81U

on pickup

on Trip

None

2561 Freeze Waveform 2 81U

on pickup

on Trip

None

2800 Breaker Failure (50BF)

2801 Function 50BF

Enabled

Disabled

2803 Pickup 50BF

5 A CT

0.25 A

Range: 0.25-5.0 A

(0.01 A steps)

A

1 A CT

0.1 A

Range: 0.02-1.0 A

(0.01 A steps)

A

2804 Delay 50BF

10 cycles

Range: 8-254 cycles

cycles

2805 Monitor 50BF

current

breaker

both

S