ISGS Settings Worksheet for
Date:
Set A
Siemens Energy & Automation, Inc.
S-7
A2500 Overfrequency (81O)
Underfrequency (81U)
A2501 Function 81O
Enabled
Disabled
A2502 Pickup 81O
62.0 Hz
Range: 60.1-65.0 Hz
(0.1 Hz steps)
Hz
A2504 Time Delay 81O
0.10 s
Range: 0-100 s (0.01 s steps),
or
∞
s
2506 Block 81O
40 V
Range: 40-120 V (1 V steps)
V
2510 Frz. Wfm1 81O
on Pickup
on Trip
None
2511 Frz. Wfm2 81O
on Pickup
on Trip
None
A2551 Function 81U
Enabled
Disabled
A2553 Pickup 81U
58.0 Hz
Range: 55.0-59.9 Hz
(0.1 Hz steps)
Hz
A2554 Delay 81U
0.10 s
Range: 0-100 s (0.01 s steps),
or
∞
s
A2556 Block 81U
40 V
Range: 40-120 V (1 V steps)
V
2560 Freeze Waveform 1 81U
on pickup
on Trip
None
2561 Freeze Waveform 2 81U
on pickup
on Trip
None
2800 Breaker Failure (50BF)
2801 Function 50BF
Enabled
Disabled
2803 Pickup 50BF
5 A CT
0.25 A
Range: 0.25-5.0 A
(0.01 A steps)
A
1 A CT
0.1 A
Range: 0.02-1.0 A
(0.01 A steps)
A
2804 Delay 50BF
10 cycles
Range: 8-254 cycles
cycles
2805 Monitor 50BF
current
breaker
both
S