Glossary – Siemens ISGS SG8158-00 User Manual
Page 110
Glossary
G-ii
Siemens Energy & Automation, Inc.
Forward Parameter setting of several ISGS functions that
allows the directional protection element to pickup on fault
current only in the direction of normal power flow.
High-Set Instantaneous Neutral or Ground Overcurrent
(50HSN) A relay function that protects against a neutral or
ground overcurrent condition. Tripping occurs when the neu-
tral or ground current exceeds the programmed pickup at
100%. When tripping occurs, the actual condition that
caused the trip is recorded in the device's nonvolatile trip log.
High-Set Instantaneous Phase Overcurrent (50HS) A
relay function that protects against a phase overcurrent con-
dition. Tripping occurs when any one phase current exceeds
the programmed pickup at 100%. When tripping occurs, the
actual condition that caused the trip is recorded in the
device's nonvolatile trip log.
Impedance Parameter of several ISGS protective functions
that set the angle used by this function. Impedance deter-
mines the direction of current flow being measured and can
be set from 0 to 90 degrees in steps of 1 degree.
Instantaneous Neutral or Ground Overcurrent (50N) A
relay function that protects against a neutral or ground over-
current condition. Tripping occurs when the neutral or
ground current exceeds the programmed pickup at 100% or
drops below the pickup at 95% for a period of time equal to
the delay time setting. The pickup must remain active for the
entire delay time for a trip to occur. If the overcurrent condi-
tion subsides in less time than the delay time, the pickup will
go inactive and the instantaneous neutral or ground overcur-
rent function will reset. When tripping occurs, the actual con-
dition that caused the trip is recorded in the device's
nonvolatile trip log.
Instantaneous Phase Overcurrent (50) A relay function
that protects against a phase overcurrent condition. Tripping
occurs when any one phase current exceeds the pro-
grammed pickup at 100% or drops below the pickup at 95%
for a period of time equal to the delay time setting. The
pickup must remain active for the entire delay time for a trip
to occur. If the overcurrent condition subsides in less time
than the delay time, the pickup will go inactive and the
instantaneous phase overcurrent function will reset. When
tripping occurs, the actual condition that caused the trip is
recorded in the device's nonvolatile trip log.
Intelligent SwitchGear System (ISGS) High-speed,
numerical, microprocessor-based protective relay designed
to be easily incorporated into a computer monitored medium
voltage power system.
ISGS see Intelligent SwitchGear System
LCD Two-line by sixteen character liquid crystal display that
allows the viewing of parameters, real-time data, keypad
entries, and messages.
logical input Input to a function internal to a relay, such as
a blocking input for a function. Logical inputs can only be
activated if matrixed to a physical input.
logical output Output of a function internal to a relay, such
as logging an event.
matrixing Process of assigning inputs (actions) to outputs
(reactions).
Negative Sequence Voltage (47N) Relay function that
protects against a negative sequence voltage condition using
a definite time or inverse time characteristic. Tripping occurs
when the percent of negative phase sequence voltage
exceeds the preset value for a specified time. This function
resets instantaneously when the negative sequence voltage
drops below pickup.
Neutral Time Overcurrent (51N) A relay function that
protects against a neutral overcurrent condition by using a
selected time overcurrent characteristics curve to determine
the trip time. Tripping occurs when the neutral current
exceeds the programmed pickup at 100% or drops below
the pickup at 95% for a period of time equal to the delay time
setting. The pickup must remain active for the entire delay
time for a trip to occur. If the overcurrent condition subsides
in less time than the delay time, the pickup will go inactive
and the neutral time overcurrent function will reset. When
tripping occurs, the actual condition that caused the trip is
recorded in the device's nonvolatile trip log.
overcurrent fault protection Process where current sig-
nals from sensors are converted to digital voltages by a resis-
tor network and analog to digital converters in a trip unit. The
digital voltages are stored in temporary memory. A protection
microprocessor reads these voltages and compares their
values to the set of values entered by the user. When the
microprocessor detects an overcurrent condition, it's soft-
ware begins to process a defined protection function. During
the process of the protection function, the microprocessor
continues monitoring the incoming current level data. If the
overcurrent condition continues until the processing is com-
pleted and the defined delay time has elapsed, a trip com-
mand is issued by the microprocessor. The trip command
causes an output signal to be sent to a coil in the tripping
actuator.
Overfrequency (81O) Relay function that protects against
an overfrequency condition. Tripping occurs when the fre-
quency exceeds the programmed overfrequency pickup for
a period of time equal to the delay time setting. The pickup
must remain active for the entire delay time for a trip to occur.
If the overfrequency condition subsides in less time than the
delay time, the pickup will go inactive and the overfrequency
function will reset. When tripping occurs, the actual condition
that caused the trip is recorded in the device's nonvolatile
trip log. Pickup occurs when the frequency in greater than
the pickup setting.
parameter set Many protective functions of an ISGS relay
offer two sets of parametersset A and set B. Each set can
be selected to be the active set that controls the relay. Sepa-
rate parameter sets are useful for seasonal or special opera-
tion settings.
G
isv3o_1.bk : isv30_gl.frm Page ii Wednesday, August 7, 1996 10:51 AM