Appendix D: Acceptance Test Procedures

68

Siemens Energy & Automation, Inc.

ISGS Acceptance Test

Undervoltage (27) Function

Set the ISGS as follows:
Parameter Set A

7103

Voltage Primary Rating 120 V

1201

Connection Line to Neutral

1202

Enable Function

2301

Time Characteristic: Inverse Time

2302

Trip on Line to Neutral

2303

Pickup Level 100 V

2304

Time Dial 5.0

2306

Trip Matrixed to Trip 1 Contact

6401

Phase

A B C

Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).

Relay Disabled contact on terminals 19 and 20 opens.

With 27 enabled, pickup LED is illuminated; relay may trip on Undervoltage before VT source is applied.

2. Connect suitable variable voltage source to terminals 41, 43, and 45 with

neutral connected to 42, 44, and 46.

3. Connect timer to Trip 1 contacts on terminals 1 and 2.

Pickup

4. Apply nominal to neutral system voltage.

Pickup LED extinguishes.

Trip LED may be reset.

5. Slowly reduce voltage until relay picks up.

Pickup LED illuminates.

Display shows PICKUP 27 P1 (2, 3).

Wisdom software records pickup in event log.

6. Return voltage to nominal value.

Pickup LED extinguishes.

Wisdom software records end of pickup.