ISGS Settings Worksheet for

Date:

Set A

S-4

Siemens Energy & Automation, Inc.

A1900 Directional Phase Time Overcurrent (67)

A1901 Function 67

Enabled

Disabled

A1902 Curve 67

Inverse

Short Inverse

Long Inverse

Moderately

Inverse

Custom

Very Inverse

Extremely Inverse Definite Inverse

Slightly Inverse

I

2

T without Limit

A1903 Pickup 67

5 A CT

0.5 A

Range: 0.5-20 A (0.1 A steps)

A

1 A CT

0.1 A

Range: 0.1-4 A (0.1 A steps)

A

A1905 Time Dial 67

0.10

Range: 0.1-9.9 (0.1 steps)

A1906 Filter 67

rms fundamental

A1907 Impedance 67

45°

Range: 0-90° (1° steps)

°

A1908 Direction 67

Normal

Reverse

1910 Freeze Waveform 1 67

on Pickup

on Trip

None

1911 Freeze Waveform 2 67

on Pickup

on Trip

None

A2000 Directional Neutral Time Overcurrent (67N)

A2001 Function 67N

Enabled

Disabled

A2002 Curve 67N

Inverse

Short Inverse

Long Inverse

Moderately

Inverse

Custom

Very Inverse

Extremely Inverse Definite Inverse

Slightly Inverse

I

2

T without Limit

A2003 Pickup 67N

5 A CT

0.5 A

Range: 0.5-20 A (0.1 A steps)

A

(PU point is 1.06

1 A CT

of PU setting).

0.1 A

Range: 0.1-4 A (0.1 A steps)

A

A2005 Time Dial 67N

0.10

Range: 0.1-9.9 (0.1 steps)

A2006 Filter 67N

rms fundamental

A2007 Impedance 67N

45°

Range: 0-90° (1° steps)

°

A2008 Direction 67N

Normal

Reverse

2010 Freeze Waveform 1 67N

on Pickup

on Trip

None

2011 Freeze Waveform 2 67N

on Pickup

on Trip

None