ISGS Settings Worksheet for
Date:
Set A
S-4
Siemens Energy & Automation, Inc.
A1900 Directional Phase Time Overcurrent (67)
A1901 Function 67
Enabled
Disabled
A1902 Curve 67
Inverse
Short Inverse
Long Inverse
Moderately
Inverse
Custom
Very Inverse
Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
A1903 Pickup 67
5 A CT
0.5 A
Range: 0.5-20 A (0.1 A steps)
A
1 A CT
0.1 A
Range: 0.1-4 A (0.1 A steps)
A
A1905 Time Dial 67
0.10
Range: 0.1-9.9 (0.1 steps)
A1906 Filter 67
rms fundamental
A1907 Impedance 67
45°
Range: 0-90° (1° steps)
°
A1908 Direction 67
Normal
Reverse
1910 Freeze Waveform 1 67
on Pickup
on Trip
None
1911 Freeze Waveform 2 67
on Pickup
on Trip
None
A2000 Directional Neutral Time Overcurrent (67N)
A2001 Function 67N
Enabled
Disabled
A2002 Curve 67N
Inverse
Short Inverse
Long Inverse
Moderately
Inverse
Custom
Very Inverse
Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
A2003 Pickup 67N
5 A CT
0.5 A
Range: 0.5-20 A (0.1 A steps)
A
(PU point is 1.06
1 A CT
of PU setting).
0.1 A
Range: 0.1-4 A (0.1 A steps)
A
A2005 Time Dial 67N
0.10
Range: 0.1-9.9 (0.1 steps)
A2006 Filter 67N
rms fundamental
A2007 Impedance 67N
45°
Range: 0-90° (1° steps)
°
A2008 Direction 67N
Normal
Reverse
2010 Freeze Waveform 1 67N
on Pickup
on Trip
None
2011 Freeze Waveform 2 67N
on Pickup
on Trip
None