Installation

6

Siemens Energy & Automation, Inc.

Mount the relay using the following steps.

1. Install the relay M1-type case in the panel opening on

the switchgear equipment.

2. Connect the case ground to the terminal lug on the

back of the M1-type case as shown in Figure 2.3.

3. Wire as described in Section 2.4.

Figure 2.3 Case Grounding

2.4 Wiring

Wire the ISGS relay after the case is installed. Connect the

wiring to the applicable terminals to support the desired fea-

tures. Refer to Figure 2.4 for terminal locations. Figure 2.5

shows the internal connections of the ISGS relay. To avoid

injury to personnel or the equipment, perform power connec-

tions after all other wiring has been completed.

Assure that all power is off before performing any wiring. Ter-

minals 1 through 20 accept ring-tongue or forked spade ter-

minals and are suitable for 14 AWG to 10 AWG wire.

Terminals 21 through 60 are for directly inserting the appro-

priate wire and are suitable for 22 AWG to 14 AWG wire.

Communications connections made to terminals 48 to 50

require shielded twisted pair wire.

CT connections should be made with the polarity end of the

CT connected to current terminal marked with an asterisk (*).

Use toothed washers to
ensure solid metal contact
through paint of cover and
panel

Case ground, #12
or braided cable to
good cubicle ground,
as short as possible

IMPORTANT:

Any unused terminals must remain discon-

nected. They are for factory use only.

Figure 2.4 Terminal Locations

20

19

18

16

14

12

17

15

13

11

10

9

8

6

4

2

7

5

3

1

Case Ground

41 VT1+
42 VT1-
43 VT2+
44 VT2-
45 VT3+
46 VT3-
47 NC (unused)
48 SEAbus Signal +
49 SEAbus Signal -
50 SEAbus Ref

BO1A

31

BO1B

32

BO2A

33

BO2B

34

AI1+

35

AI1-

36

AI2+

37

AI2-

38

AO1+

39

AO1-

40

BI1A

21

BI1B

22

BI2A

23

BI2B

24

BI3A

25

BI3B

26

BI4A

27

BI4B

28

Trip 3A 29
Trip 3B 30

Top

Relay Disabled 2

Relay Disabled 1

Impedance Sense

Impedance Source

Ground Monitor

BI T

rip

BI B Switch

Power Input +

Power Input -

T

rip 2

CTN-2

CTN-1*

CT3-2

CT3-1*

CT2-2

CT2-1*

CT1-2

CT1-1*

T

rip 1

T

rip Common

2

isv3o_1.bk : isv3oins.frm Page 6 Wednesday, August 7, 1996 10:51 AM