beautypg.com

Data acquisition – Siemens ISGS SG8158-00 User Manual

Page 51

background image

Data Acquisition

Siemens Energy & Automation, Inc.

45

7.3.2 Voltage Minimum/Maximum Log

The Voltage Minimum/Maximum Log function allows the dis-

play of minimum and maximum values measured by the

relay. The collected information is compared against previ-

ously stored values and the log is updated. All logged values

are time stamped and resetting the log (see Section 6.7) will

reset all log values. No voltages are metered unless the VT

option is installed.

The MinTHD and MaxTHD parameters (4717 and 4718) dis-

play the minimum or maximum total harmonic distortion cal-

culation for the average current. The calculation is an

estimate of the harmonics on the system rather than an

exact measurement.

7.3.3 Power Minimum/Maximum Log

The Power Minimum/Maximum Log function allows the dis-

play of minimum and maximum values measured by the

relay. The collected information is compared against previ-

ously stored values and the log is updated. All logged values

are time stamped, and resetting the log (see Section 6.6) will

reset all log values. No voltages are metered unless the VT

option is installed.

4700 Voltage Minimum/Maximum Log

Address Data

Description

4701 V12 min

Minimum phase voltage

between phases A and B

4702 V12 max

Maximum phase voltage

between phases A and B

4703 V23 min

Minimum phase voltage

between phases B and C

4704 V23 max

Maximum phase voltage

between phases B and C

4705 V31 min

Minimum phase voltage

between phases C and A

4706 V31 max

Maximum phase voltage

between phases C and A

4713 VAv min

Minimum average voltage

4714 VAv max

Maximum average voltage

4717 MinTHD

Minimum value of estimated

total harmonic distortion

4718 MaxTHD

Maximum value of estimated

total harmonic distortion

7.3.4 Frequency Minimum/Maximum Log

The Frequency Minimum/Maximum Log function allows the

display of minimum and maximum values measured by the

relay. The collected information is compared against previ-

ously stored values and the log is updated. All logged values

are time stamped, and resetting the log (see Section 6.7) will

reset all log values.

4800 Power Minimum/Maximum Log

Address Data

Description

4801 kW min

Minimum power value

4802 kW max

Maximum power value

4803 kW dem min

Minimum active power demand

value

4804 kW dem max

Maximum active power demand

value

4805 kVA min

Minimum kilovolt-ampere value

4806 kVA max

Maximum kilovolt-ampere value

4807 kVAR min

Minimum kilovolt-ampere

reactive value

4808 kVAR max

Maximum kilovolt-ampere

reactive value

4809 PF max

Maximum power factor value

4810 PF min

Minimum power factor value

4900 Frequency Metering

Address

Data

Description

4901 Fmin

Minimum frequency value

4902 Fmax

Maximum frequency value

7

isv3o_1.bk : isv3odaq.frm Page 45 Wednesday, August 7, 1996 10:51 AM