ISGS Settings Worksheet for
Date:
Set B
Siemens Energy & Automation, Inc.
S-19
B1700 Phase Time Overcurrent (51)
B1702 Curve 51
Inverse
Short Inverse
Long Inverse
Moderately
Inverse
Custom
Very Inverse
Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
B1703 Pickup 51
5 A CT
0.5 A
Range: 0.5-20 A (0.1 A steps)
A
(PU point is 1.06
1 A CT
of PU setting).
0.1 A
Range: 0.1-4 A (0.1 A steps)
A
B1705 Time Dial 51
0.1
Range: 0.1-9.9 (0.1 steps)
B1706 Filter 51
rms fundamental
B1709 Reset 51
Disk Emulation
Instantaneous
1710 Freeze Waveform 1 51
Settings displayed or changed here apply to both parameter sets
1711 Freeze Waveform 2 51
Settings displayed or changed here apply to both parameter sets
B1712 Block 51 by
None
50HS & 50HSN
50HS
50HSN
B1800 Neutral Time Overcurrent (51N)
B1801 Function 51N
Enabled Disabled
B1802 Curve 51N
Inverse
Short Inverse
Long Inverse
Moderately
Inverse
Custom
Very Inverse
Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
B1803 Pickup 51N
5 A CT
0.5 A
Range: 0.5-20 A (0.1 A steps)
A
1 A CT
0.1 A
Range: 0.1-4 A (0.1 A steps)
A
B1805 Time Dial 51N
0.1
Range: 0.1-9.9 (0.1 steps)
B1806 Filter 51N
rms fundamental
B1809 Reset 51N
Disk Emulation
Instantaneous
1810 Freeze Waveform 1 51N
Settings displayed or changed here apply to both parameter sets
1811 Freeze Waveform 2 51N
Settings displayed or changed here apply to both parameter sets
B1812 Block 51N by
None
50HS & 50HSN
50HS
50HSN
S
isv3o_1.bk : isv3o_cf.frm Page 19 Wednesday, August 7, 1996 10:51 AM