ISGS Settings Worksheet for
Date:
Set B
S-20
Siemens Energy & Automation, Inc.
B1900 Directional Time Overcurrent (67)
B1901 Function 67
Enabled
Disabled
B1902 Curve 67
Inverse
Short Inverse
Long Inverse
Moderately
Inverse
Custom
Very Inverse
Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
B1903 Pickup 67
5 A CT 0.5 A
Range: 0.5-20 A (0.1 A steps)
A
1 A CT 0.1 A
Range: 0.1-4 A (0.1 A steps)
A
B1905 Time Dial 67
0.1
Range: 0.1-9.9 (0.1 steps)
B1906 Filter 67
rms fundamental
B1907 Impedance 67
45°
Range: 0-90° (1° steps)
°
B1908 Direction 67
Normal
Reverse
1910 Freeze Waveform 1 67
Settings displayed or changed here apply to both parameter sets
1911 Freeze Waveform 2 67
Settings displayed or changed here apply to both parameter sets
B2000 Directional Neutral Time Overcurrent (67N)
B2001 Function 67N
Enabled
Disabled
B2002 Curve 67N
Inverse
Short Inverse
Long Inverse
Moderately
Inverse
Custom
Very Inverse
Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
B2003 Pickup 67N
5 A CT 0.5 A
Range: 0.5-20 A (0.1 A steps)
A
(PU point is 1.06
1 A CT
of PU setting).
0.1 A
Range: 0.1-4 A (0.1 A steps)
A
B2005 Time Dial 67N
0.1
Range: 0.1-9.9 (0.1 steps)
B2006 Filter 67N
rms fundamental
B2007 Impedance 67N
45°
Range: 0-90° (1° steps)
°
B2008 Direction 67N
Normal
Reverse
2010 Freeze Waveform 1 67N
Settings displayed or changed here apply to both parameter sets
2011 Freeze Waveform 2 67N
Settings displayed or changed here apply to both parameter sets
S
isv3o_1.bk : isv3o_cf.frm Page 20 Wednesday, August 7, 1996 10:51 AM