Protective Function Configuration

28

Siemens Energy & Automation, Inc.

When the curve is set to inverse, the Max Time parameter

(2456) sets an absolute maximum amount of time that the

function will remain in pickup regardless of the inverse curve.

The value ranges from 1 to 250 seconds and can be set in

steps of 1 second.

Blocking (2457) can be set from 40 to 120 V. Regardless of

the setting, the function is automatically blocked if the volt-

age drops below 40 V. An event will be generated when this

function is blocked due to an undervoltage condition.

Each of the two waveform capture buffers (2460 and 2461)

can be independently programmed to freeze snapshots on

pickup or trip.

The function is able to actuate any binary output contact on

pickup, and any trip or binary output contact on trip.

5.15 Overfrequency (81O)

The Overfrequency function has only a definite time charac-

teristic and causes a time-delayed trip if the system line fre-

quency rises above a set level.

The Overfrequency function can be enabled or disabled

(2501).

The function begins timing when the frequency exceeds the

pickup frequency setting (2503).

The time delay (2504) represents the time between pickup

and trip. The delay can be adjusted from 0 to 100 seconds in

steps of 0.1 second. The delay can also be set to infinity so

that the function never times out.

Blocking (2506) can be set from 40 to 120 V. Regardless of

the setting, the function is automatically blocked if the volt-

age drops below 40 V. An event will be generated when this

function is blocked due to an undervoltage condition.

Each of the two waveform capture buffers (2510 and 2511)

can be independently programmed to freeze snapshots on

pickup or trip.

The function is able to actuate any binary output contact on

pickup, and any trip or binary output contact on trip.

A2500 Overfrequency (81O)

Address Parameter

Option

2501 Function

Enabled or Disabled

2502 Pickup Nominal

frequency

60.1-65.0 Hz (0.1 Hz steps)

2504 Time Delay

0-100 s (0.01 s steps),

or infinity

2505 Blocked at

40-120 V (at VT input)

(1 V steps)

2510 Freeze Wfm1

on Pickup, on Trip, or None

2511 Freeze Wfm2

on Pickup, on Trip, or None

5.16 Underfrequency (81U)

The Underfrequency (81U) function has only a definite time

characteristic and causes a time-delayed trip if the system

line frequency drops below a set level. This function can be

useful for load shedding applications.

The Underfrequency function can be enabled or disabled

(2551).

The function begins timing when the frequency drops below

the pickup frequency setting (2553).

The time delay (2554) represents the time between pickup

and trip. The delay can be adjusted from 0 to 100 seconds in

steps of 0.1 second. The delay can also be set to infinity so

that the function never times out.

Blocking (2556) can be set from 40 to 120 V. Regardless of

the setting, the function is automatically blocked if the volt-

age drops below 40 V. An event will be generated when this

function is blocked due to an undervoltage condition.

Each of the two waveform capture buffers (2560 and 2561)

can be independently programmed to freeze snapshots on

pickup or trip.

The function is able to actuate any binary output contact on

pickup, and any trip or binary output contact on trip.

5.17 Breaker Failure (50BF)

The Breaker Failure function responds to a fault condition

where any phase current being measured by the CTs does

not drop below a programmable level. Whenever another

protective function activates the contact identified by the

breaker parameter, (usually Trip 1), this function will wait until

the set amount of time has expired. Then it checks the phase

currents. If they are not equal to or less than the set pickup

value, the function executes its defined actions.

A2500 81U Underfrequency

Address Parameter

Option

2551 Function

Enabled or Disabled

2553 Pickup Nominal

frequency

55.0-59.9 Hz (0.1 Hz steps)

2554 Time Delay

0-100 s (0.01 s steps),

or infinity

2556 Blocked at

40-120 V (at VT input)

(1 V steps)

2560 Freeze Wfm1

on Pickup, on Trip, or None

2561 Freeze Wfm2

on Pickup, on Trip, or None

5