Data Acquisition

46

Siemens Energy & Automation, Inc.

7.4 Metered Data

Metered data is stored by the ISGS relay and can be dis-

played by accessing address blocks 4100 to 4900. The dis-

play of this data does not require a password. You can

display the same data more conveniently by using Wisdom

software described in Chapter 8.

7.4.1 Current Values

The Current Metering function stores the metered current

and current demand values for the ISGS relay. The relay will

measure and display the rms values of the current for the

three phases and ground or neutral. The ISGS relay also

shows total harmonic distortion as a percentage of the fun-

damental for the three phase current inputs. This function

displays undefined when the measured components are

below the total harmonic distortion threshold.

7.4.2 Voltage Values

The Voltage Metering function allows the display of metered

voltage data for the ISGS relay. The rms voltage measure-

ments for this function depend on the selected VT connec-

tion method, either line-to-ground or line-to-line. The relay

also shows total harmonic distortion as a percentage of the

fundamental for the three phase voltage inputs. It displays

undefined when the measured components are below the

total harmonic distortion threshold. This function is only avail-

able if the voltage input option is installed.

4100 Current Metering

Address Data

Range

4101 I Phase A

0-250% I

CT

4102 I Phase B

0-250% I

CT

4103 I Phase C

0-250% I

CT

4104 I Neutral

0-250% I

CT

4105 I Average

0-250% I

CT

4106 I Demand Phase A

0-250% I

CT

4107 I Demand Phase B

0-250% I

CT

4108 I Demand Phase C

0-250% I

CT

4109 I Demand Average

0-250% I

CT

4110 THD Current

0-250% I

CT

I

CT

= primary CT rating

7.4.3 Power Values

The Power Metering function stores the metered voltage

data for the ISGS relay. This function is only available if the

voltage input option is installed.

7.4.4 Frequency Values

The Frequency Metering function allows the display of the

system frequency. This function is only available if the voltage

input option is installed.

4200 Voltage Metering

Address Data

Range

4201 V Phases A-B

10-125% Vn

4202 V Phases B-C

10-125% Vn

4203 V Phases C-A

10-125% Vn

4204 V L-L Average

10-125% Vn

4209 THD Volts

10-125% Vn

IVT = primary VT rating

4300 Power Metering

Address Data

Range

4301 kW 3-Phase

0-999,999.99 kW

4302 kW Hours

0-999,999.99 kWHR

4303 kW Demand

0-999,999.99 kWD

4304 kVA 3-Phase

0-999,999.99 kVA

4305 kVAR 3-Phase

0-999,999.99 kVAR

4306 kVAR Hours

0-999,999.99 kVARH

4307 PF

-1 — 0 — +1

4400 Frequency Metering

Address Data

Range

4401 Frequency

45-65 Hz