ISGS Settings Worksheet for
Date:
Set A
S-8
Siemens Energy & Automation, Inc.
3000 Alarm Setpoints
3100 Demand Setpoints
3101 Demand Interval
15
30
60
minutes
3102 Sync time
0
15
30
45
minutes after hour
3103 Subperiods 60
1
2
3
4
6
12
3104 Subperiods 30
1
2
3
6
3105 Subperiods 15
1
3
3106 Current Average Demand
Enabled
Disabled
3107 Current Average Demand Pickup 3000 A
Range: 0-9999 A (1 A steps)
A
3108 KW Demand
Enabled
Disabled
3109 KW Demand Pickup
100000 kW
Range: 0-999,999 kW
(1 kW steps)
kW
3200 Power Setpoints
3201 KVAR Function
Enabled
Disabled
3202 KVAR Pickup
100000 kVAR
Range: 0-999,999 kVAR
(1 kVAR steps)
kVAR
3203 KVAR Time Delay
1800 s
Range: 0-3600 s (1 s steps)
s
3204 KVA Function
Enabled
Disabled
3205 KVA Pickup
100000 kVA
Range: 0-999,999 kVA
(1 kVA steps)
kVA
3206 KVA Time Delay
1800 s
Range: 0-3600 s (1 s steps)
s
3207 PF Lead Function
Enabled
Disabled
3208 PF Lead Pickup
0.8
Range: 0.2-1.0 (0.1 steps)
3209 PF Lead Sign
Lag
Lead
3210 PF Lead Delay
1800 s
Range: 0-3600 s (1 s steps)
s
3211 PF Lag Function
Enabled
Disabled
3212 PF Lag Pickup
0.8
Range: 0.2-1.0 (0.1 steps)
3213 PF Lag Sign
Lag
Lead
3214 PF Lag Delay
1800 s
Range: 0-3600 s (1 s steps)
s