ISGS Settings Worksheet for

Date:

Set A

S-8

Siemens Energy & Automation, Inc.

3000 Alarm Setpoints

3100 Demand Setpoints

3101 Demand Interval

15

30

60

minutes

3102 Sync time

0

15

30

45

minutes after hour

3103 Subperiods 60

1

2

3

4

6

12

3104 Subperiods 30

1

2

3

6

3105 Subperiods 15

1

3

3106 Current Average Demand

Enabled

Disabled

3107 Current Average Demand Pickup 3000 A

Range: 0-9999 A (1 A steps)

A

3108 KW Demand

Enabled

Disabled

3109 KW Demand Pickup

100000 kW

Range: 0-999,999 kW

(1 kW steps)

kW

3200 Power Setpoints

3201 KVAR Function

Enabled

Disabled

3202 KVAR Pickup

100000 kVAR

Range: 0-999,999 kVAR

(1 kVAR steps)

kVAR

3203 KVAR Time Delay

1800 s

Range: 0-3600 s (1 s steps)

s

3204 KVA Function

Enabled

Disabled

3205 KVA Pickup

100000 kVA

Range: 0-999,999 kVA

(1 kVA steps)

kVA

3206 KVA Time Delay

1800 s

Range: 0-3600 s (1 s steps)

s

3207 PF Lead Function

Enabled

Disabled

3208 PF Lead Pickup

0.8

Range: 0.2-1.0 (0.1 steps)

3209 PF Lead Sign

Lag

Lead

3210 PF Lead Delay

1800 s

Range: 0-3600 s (1 s steps)

s

3211 PF Lag Function

Enabled

Disabled

3212 PF Lag Pickup

0.8

Range: 0.2-1.0 (0.1 steps)

3213 PF Lag Sign

Lag

Lead

3214 PF Lag Delay

1800 s

Range: 0-3600 s (1 s steps)

s