beautypg.com

Appendix a: trip curves & equations, A.4 i-squared-t curve, A.5 custom protective curve – Siemens ISGS SG8158-00 User Manual

Page 62: A.6 over/undervoltage curves

background image

Appendix A: Trip Curves & Equations

56

Siemens Energy & Automation, Inc.

Figure A.9 Definite Inverse Curve (SEA8)

A.4 I-Squared-T Curve

The ISGS provides an I-Squared-T characteristic in addition

to the standard inverse curves.

Equation A.4 I-Squared-T Equation

0.01

0.1

1

10

100

1

10

50

9.9

7.0

5.0

3.0

1.5

0.5

0.1

Multiples of Pickup

T

ime to T

rip (Seconds)

T

ime Dial

Trip Characteristic

Reset Characteristic

T = time to trip, in seconds

= multiple of pickup setting

D = time dial setting, 0.1 to 9.9 in steps of 0.1

t

r

= reset constant = 7.4

T

50.7D 10.14

+

i

i

p

----

 

 

2

-------------------------------------

=

For

i

ip

-----

1:

T

t

r

D

i

ip

----

2

1

-----------------------

=

<

i

ip

-----

 

 

 

Figure A.10 I-Squared-T Curve

A.5 Custom Protective Curve

The custom curve consists of up to 60 current-time pairs

corresponding to points on the time-current characteristic

curve. Current refers to multiple-of-pickup value (I/Ip) on the

horizontal axis, and time refers to time-to-trip values on the

vertical axis. Each point consists of two values (I/Ip and t),

loaded in order from lowest to highest value of I/Ip via the

SEAbus or local ports. Siemens Wisdom software is required

in order to load a custom curve. Time-to-trip has a range of

0.00 to 655.35 seconds in steps of 0.01 seconds. I/Ip has a

range of 1.1 to 20.00 in steps of 0.01. The first point in the

data set must be I/Ip=1.1, the last point must be I/Ip=20.

Points in between these two limits can be for any values of I/

Ip and t as long as the slope (

t/(

I/Ip)) of the curve

described by the points is between 0 (horizontal) and -

(ver-

tical). For input current in excess of 20 x Ip, the relay will

enter a definite time mode and the curve will be considered

to be flat (constant time) at the time value associated with I/

Ip=20. Once loaded, a custom curve is not adjustable, that is

there is no time dial adjustment.

A.6 Over/Undervoltage Curves

The ISGS provides a moderately inverse overvoltage and a

moderately inverse undervoltage protection defined by the

equation in Equation A.5 and Equation A.6. Their charac-

teristics are provided in Figure A.11 and Figure A.12.

Multiples of Pickup

T

ime to T

rip (Seconds)

T

ime Dial

1000

100

10

1

0.1

0.01

1

10

50

9.9

7.0

5.0

3.0

1.5

0.5

0.1

A

isv3o_1.bk : isv3ocrv.frm Page 56 Wednesday, August 7, 1996 10:51 AM