Appendix b: metering, B metering, B.1 accuracy – Siemens ISGS SG8158-00 User Manual
Page 64
Appendix B: Metering
58
Siemens Energy & Automation, Inc.
B Metering
B.1 Accuracy
Table B.1 Metering Accuracies
Parameter
Range
Accuracy
rms Current (L & G)
0-250% I
n
Displayed in Amperes
±1% of measurement from 50-125% of I
n
±0.5% of I
n
from 10- 50% of I
n
Average rms Current
0-250% I
n
Displayed in Amperes
±1% of measurement from 50-125% of I
n
±0.5% of I
n
from 10-50% of I
n
Ampere Demand per Phase
0.. 250% I
n
Displayed in Amperes
±1% of measurement from 50-125% of I
n
±0.5% of I
n
from 10-50% of I
n
Average Ampere Demand
0-250% I
n
Displayed in Amperes
±1% of measurement from 50-125% of I
n
±0.5% of I
n
from 10-50% of I
n
rmsVoltage (L-L and L-N)
10-125% V
n
Displayed in kV
±1% of measurement from 50-125% of V
n
±0.5% of V
n
from 10-50% of V
n
Average rms Voltage
10-125% V
n
Displayed in kV
±1% of measurement from 50-125% of V
n
±0.5% of V
n
from 10-50% of V
n
Active Power (kW)
0-999,999.99 kW
±2% of measurement from 50-125% of P
n
±0.1% of V
n
from 10-50% of P
n
1, 5
kW Demand
0-999,999.99 kWD
±2% of measurement from 50-125% of P
n
±0.1% of V
n
from 10-50% of P
n
1, 5
kW Hours
0-999,999.99 kWHR
±2% of measurement from 50-125% of P
n
±0.1% of V
n
from 10-50% of P
n
1, 3, 5
Apparent Power (kVA)
0-999,999.99 kVA
±2% of measurement from 50-125% of P
n
±0.1% of V
n
from 10-50% of P
n
1, 5
Volt-Amperes Reactive (kVAR)
0-999,999.99 kVAR
±2% of measurement from 50-125% of P
n
±0.1% of V
n
from 10-50% of P
n
1, 2, 5
kVAR Hours
0-999,999.99 kVARH
±2% of measurement from 50-125% of P
n
±0.1% of V
n
from 10-50% of P
n
1, 2, 3, 5
Power Factor
-1- 0-+1
±0.04
4
Frequency
45-65 Hz
±0.1% of reading providing voltage is 50% VT primary rating
1
Measured at PF=1. For |PF|<1, ±2% + angle error (±2% for |PF|
≥
0.7)
2
Measured at PF=0. For |PF|>0, ±2% + angle error (±2% for |PF|
≤
0.7)
3
Energy is accumulated in either kHR or MHR, selectable (parameter).
4
For power factor, 1 is considered perfect, negative is leading and positive is lagging.
5
P
n
= V
n
x I
n
, where V
n
= VT rating (120 V) and I
n
= CT rating (5A).
Note for all values: Stated accuracy applies only when the device is not in pickup. These measurements are valid over a frequency range of
45- 65Hz and include fundamental, second harmonic, and all odd harmonics up to the 13th harmonic of the fundamental line frequency.
B