beautypg.com

Data acquisition – Siemens ISGS SG8158-00 User Manual

Page 50

background image

Data Acquisition

44

Siemens Energy & Automation, Inc.

For each log the following applies:

•

The ISGS relay keeps a lifetime count of protective func-

tion trips. The trip number (address 001) is the count at

the time of the trip. The trip number cannot be reset

unless the relay is returned to the factory.

•

The pickup time (002) consists of the date and time of

the event to the nearest millisecond.

•

The pickup parameter (003) refers to the protective

function that caused the trip. Only protective function

trips are stored in the log (no breaker monitoring, set-

points, or communications trips are logged).

•

The phase parameter (004) stores the current or voltage

phase(s) that violated protective function settings.

•

I1, I2, I3, and IN parameters (005 to 008) give the cur-

rents at pickup for phases A, B, C, and the ground cur-

rent.

•

V1, V2, and V3 (009 to 011) indicate the voltage at

pickup for phases A, B, and C. If VTs are connected line-

to-line (refer to address 1202, Section 4.5, the line-to-

line voltage is displayed for phases A-B, B-C, and C-A.

•

Trip (012) displays the function that caused the trip.

•

Phase (013) indicates the phase that caused the trip.

•

I1, I2, I3, and IN (014 to 017) give the secondary cur-

rents at trip for phases A, B, C, and the ground current.

•

V1, V2, and V3 (018 to 020) indicate the voltage at

pickup for phases A, B, and C. If VTs are connected line-

to-line (refer to address 1202, Section 4.5, the line-to-

line voltage is displayed for phases A-B, B-C, and C-A.

•

Total time in pickup (021) is the total time that the relay

read the voltage above the pickup value, not the time

the breaker is told to open or actually opens. The timer

is only reset when no function is in pickup.

Events that require special attention appear in the event log

in red when displayed on a PC. For information on Wisdom

software, refer to Chapter 8.

7.3 Min/Max Logs

7.3.1 Current Minimum/Maximum Log

The Current Minimum/Maximum Log function allows the dis-

play of minimum and maximum values measured by the

relay. The collected information is compared against previ-

ously stored values and the log is updated. All logged values

are time stamped and resetting the log (see Section 6.7) will

reset all log values.

The MinTHD and MaxTHD parameters (4619 and 4620) dis-

play the minimum or maximum total harmonic distortion cal-

culation for the average current. The calculation is an

estimate of the harmonics on the system rather than an

exact measurement.

4600 Current Minimum/Maximum Log

Address Data

Description

4601 I1 min

Phase A minimum current

4602 I1 max

Phase A maximum current

4603 I2 min

Phase B minimum current

4604 I2 max

Phase B maximum current

4605 I3 min

Phase C minimum current

4606 I3 max

Phase C maximum current

4607 IN min

Ground minimum current

4608 IN max

Ground maximum current

4609 IAv min

Average minimum current

4610 IAv max

Average maximum current

4611 I1 dmin

Phase A minimum demand

current

4612 I1 dmax

Phase A maximum demand

current

4613 I2 dmin

Phase B minimum demand

current

4614 I2 dmax

Phase B maximum demand

current

4615 I3 dmin

Phase C minimum demand

current

4616 I3 max

Phase C maximum demand

current

4617 IAv dmin

Average minimum demand

current calculated

4618 IAv dmax

Average maximum demand

current calculated

4619 MinTHD

Minimum value of estimated

total harmonic distortion

4620 MaxTHD

Maximum value of estimated

total harmonic distortion

7

isv3o_1.bk : isv3odaq.frm Page 44 Wednesday, August 7, 1996 10:51 AM