Isgs settings worksheet for date: set a – Siemens ISGS SG8158-00 User Manual
Page 92
ISGS Settings Worksheet for
Date:
Set A
S-6
Siemens Energy & Automation, Inc.
A2400 Phase Sequence Voltage (47)
Negative Sequence Voltage (47N)
A2401 Function 47
Enabled
Disabled
2410 Freeze Waveform 1 47
---
on Trip
None
2411 Freeze Waveform 2 47
---
on Trip
None
A2451 Function 47N
Enabled Disabled
A2452 Curve 47N
Inverse
Definite Inverse
A2453 Pickup 47N
10%
Range: 4-40% (1% steps)
%
A2454 Time Delay 47N(Defin.)
0.00 s
Range: 0-100 s (0.01 s steps),
or
∞
s
A2455 Time Dial 47N (Inverse)
0.10
Range: 0.1-9.9 (0.1 steps)
A2456 Maximum Time (Inverse)
120 s
Range: 1-250 s (1 s steps)
s
A2457 Block 47N by
40 V
Range: 40-120 V (1 V steps)
V
2460 Freeze Waveform 1 47N
on pickup
on Trip
None
2461 Freeze Waveform 2 47N
on pickup
on Trip
None