beautypg.com

Control & communications, 2 binary inputs, 3 binary outputs – Siemens ISGS SG8158-00 User Manual

Page 39

background image

Control & Communications

Siemens Energy & Automation, Inc.

33

6.2 Binary Inputs

Binary inputs are optically-isolated voltage level sensors with

a fixed threshold. The input is considered activated if voltage

above the threshold is applied and de-activated if no voltage

or voltage below the threshold is applied.

The status of the binary inputs is monitored whether they are

configured or not. As a result, the relay logs events when any

binary input changes state (from active to de-active or vice

versa).

Actions matrixed to binary inputs have the choice of being

performed when the binary input is activated (Hi) or de-

activated (Lo). For example, BI1 >blk 50 Hi means that 50 is

blocked when BI1 is activated. And BI1 >blk 50 Lo means

that 50 is blocked when BI1 is de-activated.

The ISGS relay displays the options at each matrix position in

the sequence listed in the table below.

On power-on or reset, the relay creates an internal state

change of all binary inputs to determine whether they are

active or inactive, and it performs all actions corresponding

to their condition and matrixing accordingly.

Binary inputs can be matrixed to disable the acceptance of

communication events.

6100 Binary Inputs

Address Para-

meter

Matrix

Position

Option

Option (cont.)

6101 Input 1

001

to

010

(Options

apply to

each

matrix

position)

not matrixed

Frz.Buff1 Hi

Frz.Buff1 Lo

Frz.Buff2 Hi

Frz.Buff2 Lo

blk 47N Hi

blk 47N Lo

blk 47 Hi

blk 47 Lo

blk 81U Hi

blk 81U Lo

blk 81O Hi

blk 81O Lo

blk 50 Hi

blk 50 Lo

blk 50N Hi

blk 50N Lo

blk 50HS Hi

blk 50HS Lo

blk 50HSN Hi

blk 50HSN Lo

blk 51N Hi

blk 51N Lo

blk 59 Hi

blk 59 Lo

blk 27 Hi

blk 27 Lo

blk 67 Hi

blk 67 Lo

blk 67N Hi

blk 67N Lo

blk 50BF Hi

blk 50BF Lo

blk ComEvt Hi

blkComEvt Lo

SwitchPara Hi

SwitchPara Lo

BI1 Hi

BI1 Lo

BI2 Hi

BI2 Lo

BI3 Hi

BI3 Lo

BI4 Hi

BI4 Lo

6102 Input 2 001-010

(same as Input 1 above)

6103 Input 3 001-010

(same as Input 1 above)

6104 Input 4 001-010

(same as Input 1 above)

6.3 Binary Outputs

The ISGS relay offers two binary outputs. The options at

each matrix position are displayed in the sequence listed in

the table below.

6200 Binary Outputs

Address Para-

meter

Matrix

Position Option

Option (cont.)

6201 Output 1

(BO 1)

001

to

020

(Options

apply to

each

matrix

position)

not matrixed

BI1

BI2

BI3

BI4

Error Sum I

Error Sym I

Error Sym V

OC Pickup

OC Trip

Non OC PU

Non OC Trip

Relay Pickup

Relay Tripped

no f

f <>

50HS Trip

50HSN Trip

81O Pickup

81O Trip

UV blks 81O

81U Pickup

81U Trip

UV blks 81U

47N Pickup

47N Trip

UV blks 47N

50HS blks 50

50HSN blks 50

50 Pickup

50 Trip

50HS blks 50N

50HSN blks

50N

50N Pickup

50N Trip

50HS blks 51

50HSN blks 51

51 Pickup

51 Trip

50HS blks 51N

50HSN blks

51N

51N Pickup

51N Trip

67 Pickup

67 Trip

67N Pickup

67N Trip

27 Pickup

27 Trip

59 Pickup

59 Trip

47 Trip

OvrBrOps PU

OvrBrAmps PU

OvrAmpsDmd

PU

OvrkWDmd PU

OvrkVAR PU

OvrkVA Pickup

PFLag Pickup

PFLead Pickup

50BF Pickup

50BF Trip

TrScMon PU

TrCoilCont PU

BrMech PU

CommEvent 1

CommEvent 2

CommEvent 3

CommEvent 4

CommEvent 5

6202 Output 2

(BO 2)

001

-

020 (same as Output 1 above)

6

isv3o_1.bk : isv3oc&c.frm Page 33 Wednesday, August 7, 1996 10:51 AM