User interface – Siemens ISGS SG8158-00 User Manual
Page 17
User Interface
Siemens Energy & Automation, Inc.
11
3.4 Menu
The ISGS relay menu (or memory map) is organized in a hier-
archical structure that is made up of address blocks and
addresses. The first level consists of address blocks. Each
address block represents one complete function or two
related functions and is identified by a unique four-digit num-
ber ending in two zeros (for example, 1500). Refer to
Figure 3.1.
The second level consists of individual addresses confined to
an address block. Each address represents a part of a func-
tionthe changeable parameteror the measured value of
a displayed parameter. The parameter is identified by a
unique four-digit number that consists of the first two digits
of the address block and two digits indicating the parame-
ters number within the address block (for example, 1502).
Refer to Figure 3.1.
Figure 3.1 Example of Menu Structure Displaying Address
Blocks with Two Related Functions, an Individual Function,
and an Unavailable Function.
A complete ISGS relay menu with parameter listing is pro-
vided in Appendix C. The various parameter settings are
shown in the respective section describing the complete
function.
Only certain protective function parameters have two set-
tings. All A settings are grouped under parameter set A, and
all B settings are grouped under parameter set B. Each
parameter set automatically includes all the regular parame-
ters that can be programmed to only one setting at a time
and, therefore, apply to both sets. Examples are protective
function enable settings and matrixed output contacts such
as waveform buffers and blocking. For more information on
parameter sets, refer to Section 6.11.
Block
Function
Address
Parameter
A1500 Instantaneous
Phase Overcurrent
(50)
High-Set Instanta-
neous Phase Over-
current (50HS)
1501
1502
1504
1510
1511
1512
1551
1552
1560
1561
Function 50
Pickup 50
Delay 50
Freeze Wfm 1 50
Freeze Wfm 2 50
Block 50
Function 50HS
Pickup 50HS
Freeze Wfm 1 HS
Freeze Wfm 2 HS
A1900 Directional Phase
Time Overcurrent
(67)
1901
1902
1903
1905
1906
1907
1908
1910
1911
Function
Curve
Pickup
Time Dial
Filter
Impedance
Direction
Freeze Wfm 1
Freeze Wfm 2
A2200 Overvoltage (59)
--- ---
The LCD identifies functions that include parameters config-
urable for A and B settings by preceding the functions
address block number with the letter A or the letter B,
depending on which parameter set is currently displayed.
Refer to Figure 3.2.
Figure 3.2 LCD Display of a Function that Includes
Parameters Configurable for A and B Settings.
In addition, when scrolling through the individual parameters
of an ISGS relay, the LCD identifies each parameter that is
configurable for A and B settings by preceding the parame-
ters address number with the letter A or the letter B,
depending on which parameter set is currently displayed.
Refer to Figure 3.3
Figure 3.3 LCD Display of a Parameter that is Configurable
for A and B Settings
When accessing the ISGS relay menu through the keypad,
the Arrow keys allow scrolling through all available functions
and parameters. If an option is not installed, the LCD only
displays the address block that is reserved for this option. In
this case, second level addresses are not available.
3.5 Standard Operating Procedures
Before attempting to display or configure any of the relay
data, ensure that the relay has control power which is indi-
cated by the system LED (green) being lit.
The steps for displaying data, configuring parameters, saving
data, and switching to the alternate parameter set for either
display or configuration are described in detail in Table 3.1,
Standard Operating Procedures.
A1500 Instantaneous
Phase Overcurrent 50
A1502 Pickup 50
110A
3
isv3o_1.bk : isv3ousr.frm Page 11 Wednesday, August 7, 1996 10:51 AM