beautypg.com

Control & communications – Siemens ISGS SG8158-00 User Manual

Page 41

background image

Control & Communications

Siemens Energy & Automation, Inc.

35

The Trip Source Impedance parameter (8301) can be

enabled or disabled. When enabled, the circuit periodically

monitors the trip supply voltage (auxiliary voltage, station bat-

tery) and will perform an action (for example, close a binary

output) should the voltage drop below ANSI minimum val-

ues. Monitoring the trip source (auxiliary power) to detect

bad connections and weak batteries is done by periodically

drawing a small current from the trip supply and monitoring

the subsequent sag in the voltage. Using averaging tech-

niques, the trip source impedance can be estimated. Based

on this estimate, an error message is given if the source volt-

age drops below ANSI minimum values during a trip event.

When the function is enabled, it can cause the actuation of

any of the output contacts. This circuit can function only in

true DC trip systems. It should be disabled and the inputs left

disconnected when the device is used in AC trip systems.

The Trip Source Fail parameter of the Trip Source Impedance

function (8302), when set to yes, allows the relay fail contact

to be asserted when the monitoring function detects an error.

When set to no, the relay fail contact is not affected.

The Trip Coil Continuity function (8303), when enabled,

senses a trip coil continuity error, causes an action to be

taken, and logs the event if the 52a and 52b switches are

ever both open at the same time for more than 100 ms. No

other time delay is implemented. When the function detects

the error, the function is considered to be in pickup until the

condition is no longer present.

The Trip Coil Fail parameter of the Trip Coil Continuity func-

tion (8304), when set to yes, allows the relay fail contact to

be asserted when the monitoring function detects an error.

When set to no, the relay fail contact is not affected.

Because the 52b switch does not need to interrupt the cur-

rent through the trip coil, it provides a reliable indication of

breaker position: when it is open, the breaker is considered

closed. The practice (in DC trip systems) of placing a red sta-

tus indicator lamp in series with the trip coil allows a conve-

nient method for monitoring the continuity of the trip coil.

When the circuit breaker is closed, the 52a switch is closed

and the voltage across them and the trip coil is small

because most of the voltage drop occurs across the indicat-

ing lamp circuit. If the trip coil is open or the a-switch is

defective, an error condition exists and an alarm can be gen-

erated. An exception is a breaker withdrawn for servicing.

The Breaker Mechanism function (8305), when enabled,

senses an error in the mechanism that controls the position

of one or both switches (breaker mechanism error), causes

an action to be taken, and an event to be logged if the

switches are ever both closed for more than 100 ms. No

other time delay is implemented. When this function detects

an error, it is considered to be in pickup until the condition is

no longer present.

The ISGS relay considers the b-switch to be more reliable. If

it senses the switches both open at the same time, the

breaker is considered to have a trip coil continuity error or to

be withdrawn. The 52a switch closed and the 52b switch

open are interpreted as a closed breaker. If the relay senses

the 52a switch open and the 52b switch closed, the

breaker is considered to be open. Refer also to Table 6.1.

6.7 Logs and Breaker Monitor Reset

With the Reset function, the user can independently reset

logs and breaker monitoring functions. Performing the reset

operation for an individual category will reset all values within

that category to zero, but new values are tracked immedi-

ately. The Resets address block also includes functions to

set the number of breaker operations and the sum of inter-

rupted current on each phase.

The Trip Log reset function (8201) can be set to yes to reset

the values in all trip logs. This function requires a password.

When the parameter is activated by setting it to yes, the LCD

displays the message “IN PROGRESS” followed by the mes-

sage “SUCCESSFUL”.

Resetting the minimum and maximum logs with the Min/Max

Values reset function (8202) discards all current values, but

new minimum and maximum values are tracked immediately.

The Energy reset function (8203) resets all demand values.

The Breaker Operations reset function (8204) resets the

breaker operations counter.

The sum of interrupted current reset function resets the sum

of interrupted current for each phase (8205).

The Breaker Operations (Counter) reset function (8211) sets

the number of breaker operations, for example, when mov-

ing the breaker to a cubicle protected by an ISGS relay

where the previous breaker had a different operations count.

The Sum of Interrupted Current for phases A, B, and C reset

functions (8212, 8213, 8214) can be set from 0 to 99999 kA.

8200 Resets

Address Function

Option/Display

8201 Trip Log

yes, in progress, successful

8202 Min/Max Values

yes, successful

8203 Energy

yes, successful

8204 Breaker Ops

yes, successful

8205 Sum I interrupted

yes, in progress, successful

8211 Breaker Ops

(Counter)

0-65535

8212 Sum IL1

0-99999 kA (0.01 kA steps)

8213 Sum IL2

0-99999 kA (0.01 kA steps)

8214 Sum IL3

0-99999 kA (0.01 kA steps)

6

isv3o_1.bk : isv3oc&c.frm Page 35 Wednesday, August 7, 1996 10:51 AM