beautypg.com

Installation, 2 installation, 1 unpacking – Siemens ISGS SG8158-00 User Manual

Page 11: 2 storing, 3 mounting

background image

Installation

Siemens Energy & Automation, Inc.

5

2 Installation

This chapter explains the installation of the ISGS relay and

includes procedures for unpacking, storing, mounting, and

wiring the relay. Prior to installation, ensure that the system

power is off and that you have all required tools and test

equipment available.

2.1 Unpacking

Upon receipt of the relay, inspect the carton for signs of dam-

age. If the carton has been opened or damaged, carefully

inspect and verify the contents against the packing list. If

pieces are missing or damaged, contact the shipping agent

or your Siemens representative. Refer to Figure 2.1 to iden-

tify the different parts of the relay.

Note: To avoid damage to the relay, transport or

store the relay in the original packing mate-

rial. Always transport the cradle assembly

inside the case.

.

Figure 2.1 Case, Cradle, Paddles, and Cover of ISGS Relay

2.2 Storing

Extended storage of the relay should adhere to the following

guidelines:

•

Store the relay in a clean, dry location in the original

packing material

•

Storage temperature range is -40°F to +167°F

(-40°C

to

+75°C)

Note: This device contains electrolytic capacitors,

which can degrade over time when stored

at temperatures over 86°F (30°C). Take care

not to store the relay at high temperatures

for extended periods.

After extended storage, connect the relay to its auxiliary volt-

age source for one or two days prior to taking it into actual

service. This serves to regenerate the electrolytic capacitors

of the auxiliary supply.

2.3 Mounting

The ISGS relay is typically installed in a switchgear unit or

relay panel. The required panel opening and a side view of

the relay are shown in Figure 2.2.

Figure 2.2 Mounting Dimensions

14.25

(362.0)

7.13

(181.0)

3.03

(77.0)

6.06

(154.0)

7.31

(185.7)

14.63

(371.5)

5.69

(144.5)

2.84

(72.1)

4X .25 (6.4) DIA

7.06

(179.4)

7.06

(179.4)

6.19

(157.2)

.63

(16.0)

.31

(7.9)

.31

(7.9)

.63

(16.0)

10-32

SCREWS

10-32

SCREWS

MOUNTING PANEL

2