Appendix D: Acceptance Test Procedures
70
Siemens Energy & Automation, Inc.
ISGS Acceptance Test
Overvoltage (59) Function
Set the ISGS as follows:
Parameter Set A
7103
Voltage Primary Rating 120 V
1201
Connection Line to Neutral
1202
Enable Function
2201
Time Characteristic: Inverse Time
2202
Trip on Line to Neutral
2203
Pickup Level 100 V
2204
Time Dial per Table
2206
Trip Matrixed to Trip 1 Contact
6401
Phase
A B C
Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
Relay Disabled contact on terminals 19 and 20 opens.
2. Connect suitable variable voltage source to terminals 41, 43, and 45 with
neutral connected to 42, 44, and 46.
3. Connect a timer to the Trip 1 contacts on terminals 1 and 2.
Pickup
4. Apply nominal to neutral system voltage.
Pickup LED extinguishes.
Trip LED may be reset.
5. Slowly increase voltage until relay picks up.
Pickup LED illuminates.
Display shows PICKUP 59 P1 (2, 3).
Wisdom software records pickup in event log.
6. Return voltage to nominal value.
Pickup LED extinguishes.
Wisdom software records end of pickup.