ISGS Settings Worksheet for
Date:
Set A
S-2
Siemens Energy & Automation, Inc.
A1500 Instantaneous Phase Overcurrent (50)
High-Set Instantaneous Phase Overcurrent (50HS)
A1501 Function 50
Enabled Disabled
A1502 Pickup 50
5 A CT
1.0 A
Range: 1-120 A (0.1 A steps)
A
1 A CT
0.2 A
Range: 0.2-24 A (0.1 A steps)
A
A1504 Time Delay 50
0.00 s
Range: 0-60 s (0.01 s steps)
s
1510 Freeze Waveform 1 50
on pickup
on Trip
None
1511 Freeze Waveform 2 50
on pickup
on Trip
None
A1512 Block 50 by
None
50HS & 50HSN
50HS
50HSN
A1551 Function 50HS
Enabled Disabled
A1552 Pickup 50HS
5 A CT
5.0 A
Range: 5-120 A (0.1 A steps)
A
1 A CT
0.2 A
Range: 0.2-24 A (0.1 A steps)
A
1560 Freeze Waveform 1 50HS
---
on Trip
None
1561 Freeze Waveform 2 50HS
---
on Trip
None
A1600 Instantaneous Neutral or Ground Overcurrent (50N)
High-Set Instantaneous Neutral or Ground Overcurrent (50HSN)
A1601 Function 50N
Enabled Disabled
A1602 Pickup 50N
5 A CT
1.0 A
Range: 1-120 A (0.1 A steps)
A
1 A CT
0.2 A
Range: 0.2-24 A (0.1 A steps)
A
A1604 Time Delay 50N
0.00 s
Range: 0-60 s (0.01 s steps)
s
1610 Freeze Waveform 1 50N
on Pickup
on Trip
None
1611 Freeze Waveform 2 50N
on Pickup
on Trip
None
A1612 Block 50N by
None
50HS & 50HSN
50HS
50HSN
A1651 Function 50HSN
Enabled Disabled
A1652 Pickup 50HSN
5 A CT
5.0 A
Range: 5-120 A (0.1 A steps)
A
1 A CT
0.2 A
Range: 0.2-24 A (0.1 A steps)
A
1660 Freeze Waveform 1 50HSN
---
on Trip
None
1661 Freeze Waveform 2 50HSN
---
on Trip
None