ISGS Settings Worksheet for

Date:

Set A

S-2

Siemens Energy & Automation, Inc.

A1500 Instantaneous Phase Overcurrent (50)

High-Set Instantaneous Phase Overcurrent (50HS)

A1501 Function 50

Enabled Disabled

A1502 Pickup 50

5 A CT

1.0 A

Range: 1-120 A (0.1 A steps)

A

1 A CT

0.2 A

Range: 0.2-24 A (0.1 A steps)

A

A1504 Time Delay 50

0.00 s

Range: 0-60 s (0.01 s steps)

s

1510 Freeze Waveform 1 50

on pickup

on Trip

None

1511 Freeze Waveform 2 50

on pickup

on Trip

None

A1512 Block 50 by

None

50HS & 50HSN

50HS

50HSN

A1551 Function 50HS

Enabled Disabled

A1552 Pickup 50HS

5 A CT

5.0 A

Range: 5-120 A (0.1 A steps)

A

1 A CT

0.2 A

Range: 0.2-24 A (0.1 A steps)

A

1560 Freeze Waveform 1 50HS

---

on Trip

None

1561 Freeze Waveform 2 50HS

---

on Trip

None

A1600 Instantaneous Neutral or Ground Overcurrent (50N)

High-Set Instantaneous Neutral or Ground Overcurrent (50HSN)

A1601 Function 50N

Enabled Disabled

A1602 Pickup 50N

5 A CT

1.0 A

Range: 1-120 A (0.1 A steps)

A

1 A CT

0.2 A

Range: 0.2-24 A (0.1 A steps)

A

A1604 Time Delay 50N

0.00 s

Range: 0-60 s (0.01 s steps)

s

1610 Freeze Waveform 1 50N

on Pickup

on Trip

None

1611 Freeze Waveform 2 50N

on Pickup

on Trip

None

A1612 Block 50N by

None

50HS & 50HSN

50HS

50HSN

A1651 Function 50HSN

Enabled Disabled

A1652 Pickup 50HSN

5 A CT

5.0 A

Range: 5-120 A (0.1 A steps)

A

1 A CT

0.2 A

Range: 0.2-24 A (0.1 A steps)

A

1660 Freeze Waveform 1 50HSN

---

on Trip

None

1661 Freeze Waveform 2 50HSN

---

on Trip

None