Hardware Configuration

18

Siemens Energy & Automation, Inc.

4.4 CT Configuration

The CT Configuration function allows you to set up the ISGS

relay to match the phase CT primary rating, the neutral or

ground CT primary rating, and the CT input’s normal power

flow setting of your system. For CT connections refer to

Figure 4.8.

The phase (1101) and neutral/ground (1102) CT primary rat-

ings are independently configurable. However, when a resid-

ual sensing method is used for ground fault protection, the

primary current ratings for the neutral CT and the phase CT

must be equal. The CT secondary ratings (1A or 5A) are set

at the factory and are not changeable from the front panel.

Power flow is also referred to as top feed or bottom feed. If

the power enters the polarity mark on the CTs, set the Power

Flow parameter (1104) to Normal. If power leaves the polarity

mark, enter Reverse. Figure 4.6 illustrates examples of nor-

mal and reverse power flow.

1100 CT Configuration

Address Parameter

Options

1101 Phase CT Primary

Rating

5-8000 A (1 A steps)

1102 Neutral or Ground

CT Primary Rating

5-8000 A (1 A steps)

1104 Power Flow

Normal or Reverse

Figure 4.6 Normal/Reverse Power Flow

4.5 VT Configuration

Use this address block to configure the ISGS relay to match

the VT primary rating and the VT connection setting for your

system. These settings are available only if the voltage input

option is installed on the relay.

ISGS

ISGS

Main Bus

Power

Power

Normal Power Flow

(Into CT Polarity Mark)

Reverse Power Flow

(Out of CT Polarity Mark)