Glossary

G-iv

Siemens Energy & Automation, Inc.

trip to occur. If the underfrequency condition subsides in less

time than the delay time, the pickup will go inactive and the

underfrequency function will reset. When tripping occurs, the

actual condition that caused the trip is recorded in the

device's nonvolatile trip log. Pickup occurs when the fre-

quency in greater than the pickup setting.

Undervoltage (27) Relay function that protects against a

line-to-line undervoltage condition. Tripping occurs when the

rms value of any one line-to-line voltage drops below the

programmed undervoltage pickup for a period of time equal

to the delay time setting. The pickup must remain active for

the entire delay time for a trip to occur. If the undervoltage

condition subsides in less time than the delay time, the

pickup will go inactive and the undervoltage function will

reset. When tripping occurs, the actual condition that caused

the trip is recorded in the device's nonvolatile trip log. Pickup

occurs when any one line-to-line voltage is less than the

pickup setting.

value supervision The ability of the ISGS relay to monitor

its own input and measurement functions for problems.

Voltage Balance Relay function that protects against an

unbalance in the phase voltages. The function monitors the

phase voltages for approximate balance (of equal magni-

tude). Balance is defined as the ratio of minimum to maxi-

mum voltage, where the maximum voltage is the largest and

the minimum voltage the smallest of the three phase volt-

ages. The voltage is considered balanced and will not cause

an alarm if the voltage min/max ratio is larger than the volt-

age balance factor. The voltage balance factor indicates the

amount of unbalance tolerated before the function generates

an alarm. The function monitors for balance when the maxi-

mum voltage is larger than the voltage balance pickup value.

An alarm occurs when the min/max ration is smaller than the

voltage balance factor.

VT Configuration A function to set up an ISGS relay with

voltage input option to match VT primary rating and VT con-

nection settings of an electrical distribution system.

Warning Indicates a potentially hazardous situation which,

if not avoided, could result in death or serious injury.

G