Matrixing Procedure

The following steps provide a detailed description on how to

matrix the ISGS relay manually using the front panel LCD and

keypad. Before matrixing the relay, ensure that power is

applied to the relay which is indicated by the lit system LED

(green).

Table 6.1 Matrixing Procedure

How to Matrix Inputs to Outputs

Step

Description

1

Press Direct Addr key; enter block address of one of the

matrix functions (6100, 6200, or 6400) using the numeric

keypad; press Enter key.
OR
Press Direct Addr key; enter the address of the desired

parameter using the numeric keypad; press Enter key.

Skip to step 4.
A complete list of ISGS relay parameters is provided in

Appendix C.

2

Use Single Arrow keys to scroll to the desired address.

3

Press F key once; use Single Arrow keys to scroll to the

desired matrix position (001-020)

4

Press Password key; enter your level 3 password fol-

lowed by Enter key. The message “PW THREE

ACCEPTED” appears. Press Enter key again to return to

the screen displayed last before password entry.
For password levels, proper password entry, and display

messages, refer to Section 3.3.

5

The display cursor located next to the address is blinking

(otherwise repeat step 4). Press No key until the desired

parameter option appears on display. Press Enter key to

set the displayed option.
Your settings can be undone any time while still in the

same address block by simply returning to the parameter

and assigning a new value.
Use Single Arrow keys to move to the next matrix posi-

tion to change additional parameters, or proceed to the

next step.

6

Press F key. At the blinking cursor position, the letter F is

displayed. Press Enter key. Message “SAVE NEW SET-

TINGS?” appears.

7

Press Yes key followed by Enter key to save settings and

reset relay to new parameters. Message “NEW SET-

TINGS SAVED” appears.
Press No key to abort any changes made. Message

“SAVING PROCEDURE ABORTED” appears.

8

Press Enter key to return to screen displayed last before

starting saving procedure.

Wisdom Software

While the ISGS relay can be matrixed manually using the

keypad and LCD, Wisdom configuring and analysis software

allows faster and easier configuration by connecting a PC

installed to either data port. For data port connections refer

to Section 2.5.1. All binary inputs, binary outputs, and the

trip contacts can be simply checked off inside the configura-

tion window of protective and other functions. Refer to

Chapter 8 for more description of how this can be done with

Wisdom software.