ISGS Settings Worksheet for
Date:
Set B
S-22
Siemens Energy & Automation, Inc.
B2400 Phase Sequence Voltage (47)
Negative Sequence Voltage (47N)
B2401 Function 47
Enabled
Disabled
2410 Freeze Waveform 1 47
Settings displayed or changed here apply to both parameter sets
2411 Freeze Waveform 2 47
Settings displayed or changed here apply to both parameter sets
B2451 Function 47N
Enabled
Disabled
B2452 Curve 47N
Inverse
Definite Inverse
B2453 Pickup 47N
10%
Range: 4-40% (1% steps)
%
B2454 Time Delay 47N(Defin.)
0.00 s
Range: 0-100 s (0.01 s steps),
or
∞
s
B2455 Time Dial 47N (Inverse)
0.1
Range: 0.1-9.9 (0.1 steps)
B2456 Maximum Time (Inverse)
120 s
Range: 1-250 s (1 s steps)
s
B2457 Block 47N by
40 V
Range: 40-120 V (1 V steps)
V
2460 Freeze Waveform 1 47N
Settings displayed or changed here apply to both parameter sets
2461 Freeze Waveform 2 47N
Settings displayed or changed here apply to both parameter sets
B2500 Overfrequency (81O)
Underfrequency (81U)
B2501 Function 81O
Enabled
Disabled
B2502 Pickup 81O
62.0 Hz
Range: 60.1-65.0 Hz
(0.1 Hz steps)
Hz
B2504 Time Delay 81O
0.10 s
Range: 0-100 s (0.01 s steps),
or
∞
s
2506 Block 81O
40 V
Range: 40-120 V (1 V steps)
V
2510 Frz. Wfm1 81O
Settings displayed or changed here apply to both parameter sets
2511 Frz. Wfm2 81O
Settings displayed or changed here apply to both parameter sets
B2551 Function 81U
Enabled
Disabled
B2553 Pickup 81U
58.0 Hz
Range: 55.0-59.9 Hz
(0.1 Hz steps)
Hz
B2554 Delay 81U
0.10 s
Range: 0-100 s (0.01 s steps),
or
∞
s
B2556 Block 81U
40 V
Range: 40-120 V (1 V steps)
V
2560 Freeze Waveform 1 81U
Settings displayed or changed here apply to both parameter sets
2561 Freeze Waveform 2 81U
Settings displayed or changed here apply to both parameter sets
S