beautypg.com

Assigning programs to mainlines, Setting up the mainline operating limits – Baseline Systems BaseStation 3200 V12 User Manual

Page 74

background image

BaseStation 3200 Advanced Irrigation Controller Manual

Assigning Programs to Mainlines

The BaseStation 3200 supports 99 programs and 8 mainlines. By default, the mainlines are

numbered in the controller from 1 – 8 regardless of whether your system has more than one. All

programs are automatically assigned to mainline #1, but you can change the settings to match your

irrigation system.

1. Turn the dial to the Flow position.

2. Press the Next button to highlight the Assign

Programs to Mainlines option.

3. Press the Enter button. The Progs to Mainline

screen displays.

4. In the Program column, press the + or

button to highlight the program that you

want to assign to a mainline.

5. Press the Next button to move to the

Mainline column, and then press the + or

button to highlight the mainline that you

want to assign to that program.

6. Press the Previous button to return to the Program column.

7. Repeat steps 4 - 6 until you have assigned all programs to the corresponding mainlines.

Setting Up the Mainline Operating Limits

The mainline is the primary water management feature in your irrigation system. In the

BaseStation 3200, you can configure the following settings for the mainline in order to better

manage flow in your irrigation system.

Note: The step-by-step procedure for setting up the mainline is on page 70.

Design Flow GPM – This field is the flow rating for the mainline in gallons per minute (GPM).

This flow is likely different from the design flow of the POC/flow device. When a mainline has

multiple POCs with different capacities, the controller uses the constrained design flow to

determine the actual available flow for watering.

For example, consider the following design flows:

Flow Device #1 = 50 GPM

Flow Device #2 = 75 GPM

Mainline #1 = 100 GPM

In the example, the controller would use 100 GPM for managing zone concurrency unless

flow device #2 was shut off (over budget or lower priority). In this case, the controller would

use 50 GPM.

Page 68