Troubleshooting diagram 5 – IDEC MicroSmart User Manual
Page 492
![background image](/manuals/350368/492/background.png)
29: T
ROUBLESHOOTING
29-12
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
Troubleshooting Diagram 5
Does the monitored
output turn on and
off?
YES
NO
YES
NO
YES
Call IDEC for assistance.
NO
Are output allocation
numbers correct?
Is the output LED on?
Make sure of correct output
wiring.
Correct the program.
The output circuit in the CPU or
output module is damaged.
Replace the module.
END
Output does not operate normally.
Check the output allocation
numbers.
Monitor the output using
WindLDR.
Click the PLC Star t button in
WindLDR on a computer con-
nected to the
MicroSmart
.
Note: To access the PLC Star t button, from the WindLDR
menu bar, select Online > Download Program.
NO
YES
Is the RUN LED on?