As-i – IDEC MicroSmart User Manual
Page 473
![background image](/manuals/350368/473/background.png)
28: AS-I
NTERFACE
M
ASTER
C
OMMUNICATION
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
28-33
Monitor AS-Interface Slave
While the
MicroSmart
is communicating with AS-Interface slaves through the AS-Interface bus, operating status of AS-
Interface slaves can be monitored using
WindLDR
on a computer. Output statuses and parameter image (PI) can also be
changed using
WindLDR
.
To open the Monitor AS-Interface Slaves dialog box, from the
WindLDR
menu bar, select
Online
>
Monitor
. From the
WindLDR
menu bar, select
Online
, and select
Monitor AS-Interface Slaves
in the pull-down menu.
Change Slave Output Statuses and Parameters
The output statuses and parameter image (PI) of the slaves connected to the AS-Interface master module can be changed.
To open the Slave Status dialog box, click the output of a required slave address in the Monitor AS-Interface Slaves dialog
box. Then, click the On or Off button to change the statuses of outputs DO0 through DO3 and parameters P0 through P3 as
required. Click
Store
to save the changes to the slave module.
If the command is not processed correctly, the error message “AS-Interface Master Error” and an error code will appear.
See page 28-34.
The output statuses and parameters cannot be changed in the following cases.
Dialog Box
Button
Description
Monitor AS-Interface Slaves
Switch Slaves
Switches between Slave A screen and Slave B screen.
Close
Closes the window.
Help
Displays explanations for functions on the screen.
Slave Status
Store
Stores output statuses and parameters to the slave.
Close
Closes the window.
Error Code
Description
1
•
An error was found on the expansion I/O bus.
7
•
The AS-Inter face master module is in local mode.
8
•
Attempt was made to change the parameters of a slave which did not exist.
Parameter
Image
(PI)