IDEC MicroSmart User Manual
Page 482
![background image](/manuals/350368/482/background.png)
29: T
ROUBLESHOOTING
29-2
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
3. Under the Error Status in the PLC Status dialog box, click the Details button. The PLC Error Status screen appears.
Clearing Error Codes from WindLDR
After removing the cause of the error, clear the error code using the following procedure:
1. From the
WindLDR
menu bar, select Online > Monitor. The monitor mode is enabled.
2. From the
WindLDR
menu bar, select Online > PLC Status. The PLC Status dialog box appears.
3. Under the Error Status in the PLC Status dialog box, click the Clear button.
This procedure clears the error code from special data register D8005 (general error code), and the error code is cleared
from the PLC Status dialog box.
Clear Button
Error Code Cleared