Dual / teaching timer instructions, Dtml (1-sec dual timer), Dtim (100-ms dual timer) – IDEC MicroSmart User Manual
Page 375: Dtmh (10-ms dual timer), Dtms (1-ms dual timer), Eaching, Imer, Nstructions
![background image](/manuals/350368/375/background.png)
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
22-1
22: D
UAL
/ T
EACHING
T
IMER
I
NSTRUCTIONS
Introduction
Dual timer instructions generate ON/OFF pulses of required durations from a designated output, internal relay, or shift
register bit. Four dual timers are available and the ON/OFF duration can be selected from 1 ms up to 65535 sec.
Teaching timer instruction measures the ON duration of the start input for the teaching timer instruction and stores the
measured data to a designated data register, which can be used as a preset value for a timer instruction.
DTML (1-sec Dual Timer)
DTIM (100-ms Dual Timer)
DTMH (10-ms Dual Timer)
DTMS (1-ms Dual Timer)
Applicable CPU Modules
FC4A-C10R2/C
FC4A-C16R2/C
FC4A-C24R2/C
FC4A-D20K3/S3
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
—
—
—
—
X
While input is on, destination operand D1 repeats to turn on
and off for a duration designated by operands S1 and S2,
respectively.
The time range is 0 through 65535 sec.
S1
*****
D1
*****
DTML
S2
*****
D2
*****
While input is on, destination operand D1 repeats to turn on
and off for a duration designated by operands S1 and S2,
respectively.
The time range is 0 through 6553.5 sec.
S1
*****
D1
*****
DTIM
S2
*****
D2
*****
While input is on, destination operand D1 repeats to turn on
and off for a duration designated by operands S1 and S2,
respectively.
The time range is 0 through 655.35 sec.
S1
*****
D1
*****
DTMH
S2
*****
D2
*****
While input is on, destination operand D1 repeats to turn on
and off for a duration designated by operands S1 and S2,
respectively.
The time range is 0 through 65.535 sec.
S1
*****
D1
*****
DTMS
S2
*****
D2
*****