Lcd display – Yaskawa iQpump Micro User Manual
Page 93

u
LCD Display
Figure 4.6 LCD Display
Table 4.3 Display and Contents
No.
Name
Display
Content
1
Operation Mode Menus
MODE
Displayed when in Mode Selection.
QMONI: Use F1/F2 Instructions to access the Quick Monitors.
MENU: Use UP/
DWN
Instructions to access the next menu item.
MONITR
Displayed when in Monitor Mode.
VERIFY
Indicates the Verify Menu.
PRMSET
Displayed when in Parameter Setting Mode.
A.TUNE
Displayed during Auto-Tuning.
SETUP
Displayed when in Setup Mode.
2
Mode Display Area
DRV
Displayed when in Drive Mode.
PRG
Displayed when in Programming Mode.
3
Ready
Rdy
Indicates the drive is ready to run.
4
Data Display
—
Displays specific data and operation data.
5
Frequency
Reference
Assignment
<1>
OPR
Displayed when the frequency reference is assigned to the HOA keypad.
COM
Displayed when the frequency reference is assigned to the MEMOBUS/Modbus
Communication Inputs of the drive.
OP
Displayed when the frequency reference is assigned to option card connected to the drive.
AI
Displayed when the function reference is assigned to an analog input.
OFF
Displayed when HAND mode is OFF.
6
LOCAL/REMOTE
Display
<2>
RSEQ
Blinks when the Run command is supplied from a remote source.
LSEQ
Displayed when the Run command is supplied from the HOA keypad.
RREF
Blinks when the Run command is supplied from a remote source.
LREF
Displayed when the Run command is supplied from the HOA keypad.
7
Function Key 2
(F2)
<-MONITOR->
Pressing
F2
displays the next Quick Monitor.
DATA
Pressing
F2
scrolls to the next display.
→
Pressing
F2
scrolls the cursor to the right.
RESET
Pressing
F2
resets the existing drive fault error.
Monitor
Pressing
F2
switches Monitor mode.
8
FWD/REV
FWD
Indicates forward motor operation.
REV
Indicates reverse motor operation.
4.5 Using the Optional HOA Keypad
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
93
4