Table B.4 Three-Phase, 200 V Class Drives Default Settings by Drive Capacity
No.
Description
Unit
Default Settings
−
Model
−
2V0006
2V0010
2V0012
2V0020
2V0030
o2-04
Drive Model Selection
Hex
63
65
66
68
6A
E2-11
Motor Rated Power
kW
1.1
2.2
3.0
5.5
7.5
b3-06
Speed Search current 1
−
0.5
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
–
0.5
0.5
0.5
0.5
0.5
C6-02
Carrier frequency
−
7
7
7
7
7
E2-01
Motor rated current
A
4.9
8.5
11.4
19.6
26.6
E2-02
Motor rated slip
Hz
2.6
2.9
2.7
1.5
1.3
E2-03
Motor no-load current
A
2.3
3.0
3.7
5.1
8.0
E2-05
Motor line-to-line resistance
Ω
3.577
1.601
1.034
0.399
0.288
E2-06
Motor leakage inductance
%
18.5
18.4
19
18.2
15.5
E2-10
Motor Iron Loss
W
38
77
91
172
262
L2-02
Momentary power loss ride-through time
s
0.2
0.3
0.5
1
1.0
L2-03
Momentary power loss Baseblock time
s
0.4
0.5
0.5
0.7
0.8
L2-04
Momentary power loss voltage recovery time
s
0.3
0.3
0.3
0.6
0.6
L2-05
Uv detection voltage
V dc
190
190
190
190
190
L3-24
Motor acceleration time
s
0.142
0.145
0.145
0.168
0.175
L8-02
Overheat alarm level
°C
100
100
100
110
115
L8-09
Ground fault selection
−
0
0
0
0
1
L8-38
Carrier frequency reduction selection
−
1
1
1
1
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
B.16 Defaults by Drive Model