Digital Operator Display

Fault Name

CPF24

Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).

Cause

Possible Solution

Hardware is damaged

Replace the drive.

Digital Operator Display

Fault Name

CPF25

Terminal Board Not Connected

Cause

Possible Solution

Terminal board is not connected correctly Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.

Digital Operator Display

Fault Name

CPF26 to CPF35

CPF40 to CPF43

Control Circuit Error
CPU error

Cause

Possible Solution

Hardware is damaged

Replace the drive.

Digital Operator Display

Fault Name

E5

SI-T3 Watchdog Timer Error
The watchdog timed out.

Cause

Possible Solution

Data has not been received from the PLC Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and

proceed to phase 3. Refer to the SI-T3 Option Technical Manual for more details on troubleshooting.

Digital Operator Display

Fault Name

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solution

An external fault was received from the

PLC and F6-03 is set to a value other than

3.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

Digital Operator Display

Fault Name

EF1

Pump Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

Pump Fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

Pump Fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

Pump Fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

Pump Fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

Pump Fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

Pump Fault (input terminal S7)
External fault at multi-function input terminal S7.

Cause

Possible Solution

An external device tripped an alarm

function

Remove the cause of the external fault and reset the fault.

Wiring is incorrect

• Properly connect the signal lines to the terminals assigned for external fault detection

(H1-oo = 20 to 2F).

• Reconnect the signal line.

5.2 Fault Detection

168

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual