Digital Operator Display

Minor Fault Name

TdE

Time Data Error

Cause

Possible Solution

An error has occurred in the Real-Clock

Time function of the HOA keypad.

Replace the HOA keypad. For instructions on replacing the HOA keypad, contact Yaskawa or your nearest

sales representative.

Digital Operator Display

Minor Fault Name

TrPC

IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.

Cause

Possible Solution

IGBTs have reached 90% of their expected

performance life.

Replace the drive.

Digital Operator Display

Minor Fault Name

UL3

Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable

time (L6-03).

Cause

Possible Solution

Parameter settings are not appropriate for

the load

Check the settings of parameters L6-02 and L6-03.

There is a fault on the machine side

Check the load for any problems.

Digital Operator Display

Minor Fault Name

UL4

Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable

time (L6-06).

Cause

Possible Solution

Parameter settings are not appropriate for

the load

Check L6-05 and L6-06 settings

There is a fault on the machine side

Check the load for any problems.

Digital Operator Display

Minor Fault Name

UL6

Underload Det 6

Motor Underload
The load has fallen below the underload curve defined in L6-14.

Cause

Possible Solution

The output current has fallen below the

motor underload curve defined in L6-14 for

longer than the time set to L6-03

Adjust the value set to L6-14 so that output current remains above the motor underload curve during normal

operation.

Digital Operator Display

Minor Fault Name

Uv

Undervoltage
One of the following conditions was true when the drive was stopped and a Run command was entered:
• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was opened.
• Low control drive input power voltage. This alarm outputs if L2-01

≠0 and DC bus voltage < L2-05.

Cause

Possible Solution

Phase loss in the drive input power.

Check for wiring errors in the main circuit drive input power. Correct the wiring.

Loose wiring in the drive input power

terminals.

• Ensure the terminals have been properly tightened.
Apply the tightening torque to the terminals as specified.

Refer to Wire Gauges and Tightening

Torques on page 70

for details.

There is a problem with the drive input

power voltage.

• Check the voltage.
• Lower the voltage of the drive input power so that it is within the limits listed in the specifications.

Drive internal circuitry is worn.

• Check the maintenance time for the capacitors (U4-05).
• Replace the drive if U4-05 exceeds 90%.

The drive input power transformer is too

small and voltage drops when the power is

switched on.

• Check for an alarm when the magnetic contactor, line breaker, and leakage breaker are closed.
• Check the capacity of the drive input power transformer.

Air inside the drive is too hot.

Check the temperature inside the drive.