Figure 4.15, U5-99, U9-02 – Yaskawa iQpump Micro User Manual

Page 112

background image

R+

S+

R-

S-

Drive 3

R+

S+

R-

S-

Drive 2

R+

S +

R-

S-

Drive 1

Figure 4.15 Daisy Chain Three Drives

Setting the Drive Networking Parameters

1.

1. Set parameter H5-01, Serial Node Address, on each drive.

Note:

For optimal performance, use consecutive numbers starting from 1. Parameter setting H5-01 must be unique for each drive.

2.

Set parameter P9-25, Highest Node Address, on each drive.

Note:

For optimal performance, set to highest H5-01 value. This setting must be the same for all the drives on the network.

3.

Set P1-01 to 3 (MEMOBUS/Modbus Network) on all the drives.

4.

Cycle main power to all networked drives.

Note:

The H5-01 setting will not take effect until power is cycled to the drive and may cause communication errors and unexpected

behavior.

Verifying Drive Network Communications

Access monitor U9-02, Network Activity, and verify:
• No drives have a value of 0 <->
• All drives are receiving valid data indicated by a regular change in the monitor value.
• At least one drive has the unit , while the others have the unit <+>.

Table 4.9 Network Connectivity Information

Network State

Top Line on Home Screen

(o1-12 = 1)

U9-02 Network Activity

Drive is the Master and is

communicating with

another drive.

Pump Off Network

CONNECTED

<- MONITOR - >

U5-99=

U1-02=

U1-91=

100.0

PSI

0.00Hz

62.8PSI

Network Activity

U9-02=

U1-02=

U1-91=

9453

0.00Hz

62.8PSI

- MONITR -

DRV RDY

Home

FWD

Drive is a node on the

network and is

communicating with a

Master.

Pump Off Network

<+> CONNECTED

<- MONITOR - >

U5-99=

U1-02=

U1-91=

100.0

PSI

0.00Hz

62.8PSI

Network Activity

U9-02=

U1-02=

U1-91=

324

<+>

0.00Hz

62.8PSI

- MONITR -

DRV RDY

Home

FWD

Drive is not able to

communicate to any other

drives.

Pump Off Network

<-> DISCONNECTED

<- MONITOR - >

U5-99=

U1-02=

U1-91=

100.0

PSI

0.00Hz

62.8PSI

Network Activity

U9-02=

U1-02=

U1-91=

0

<->

0.00Hz

62.8PSI

- MONITR -

DRV RDY

Home

FWD

If a drive displays U9-02 = 0 <->:

4.7 iQpump Presets and Functions

112

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual