Digital Operator Display
Minor Fault Name
Low Water in Tank
(LWT)
Low Water in Tank
Cause
Possible Solution
The water level in the tank is too low.
Shown when P4-24 = 2 and when the digital
input has been active (closed for P4-21 = 0,
or open for P4-21 = 1) for the time set in
P4-22.
• Check pressure switch contact for correct operation.
• Check control wiring to drive terminal strip from pressure switch contact.
• Check to make sure that suction pressure is present by means of a separate measuring device.
• Raise the water level.
Digital Operator Display
Minor Fault Name
LT-1
Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.
Note:
An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and H2-oo =
10) are set.
Cause
Possible Solution
The cooling fan has reached 90% of its
expected performance life.
Replace the cooling fan and set o4-03 to 0 to reset the Maintenance Monitor.
Digital Operator Display
Minor Fault Name
LT-2
Capacitor Maintenance Time
The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
Cause
Possible Solution
The main circuit and control circuit
capacitors have reached 90% of their
expected performance lives.
Replace the drive.
Digital Operator Display
Minor Fault Name
LT-3
Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
Cause
Possible Solution
The DC bus soft charge relay has reached
90% of expected performance life.
Replace the drive.
Digital Operator Display
Minor Fault Name
LT-4
IGBT Maintenance Time (50%)
IGBTs have reached 50% of their expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
Cause
Possible Solution
IGBTs have reached 50% of their expected
performance life.
Check the load, carrier frequency, and output frequency.
Digital Operator Display
Minor Fault Name
NETSCAN
Waiting for Master
(NETSC)
NETSCAN
Drive is waiting for a message from the master.
Cause
Possible Solution
No message was received from the master
within the time set in P9-28.
• Increase the P9-26 setting to account for network latency.
• Verify that there is a drive on the network with parameter P1-01 set to 3 and P9-27 to 0.
• Check network connections and verify H5-01 and P9-25 settings for all drives on the network.
Digital Operator Display
Minor Fault Name
NMS
SetPoint Not Met
(NOTSP)
Not Maintaining Setpoint
The setpoint cannot be maintained and P1-17 is set to 1.
Cause
Possible Solution
5.3 Alarm Detection
186