8 detailed iqpump parameter descriptions – Yaskawa iQpump Micro User Manual
Page 145

Setting 14: User-Set Speed Agree 2 (f
ref
/f
set
Agree 2)
The output closes when the actual output frequency and the frequency reference are within the speed agree width (L4-04) of
the programmed speed agree level (L4-03).
Status
Description
Open
Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-03 ±L4-04.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
Frequency reference
+
L4-04
Frequency reference – L4-04
L4-03
L4-03
+
L4-04
L4-03 – L4-04
Frequency
reference
0 Hz
OFF
OFF
ON
ON
Frequency reference
During
Forward
Output frequency
Output frequency
User Set
Speed Agree 2
Figure 4.50 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Setting 15: Frequency Detection 3
The output opens when the output frequency rises above the detection level set in L4-03 plus the detection with set in L4-04.
The terminal remains open until the output frequency or motor speed falls below the level set in L4-03. The detection level
L4-03 is a signed value; detection works in the specified direction only.
Status
Description
Open
Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.
L4-04
Frequency
detection 3
ON
OFF
L4-03
Output Frequency
or Motor Speed
Figure 4.51 Frequency Detection 3 Example with a Positive L3-04 Value
Setting 16: Frequency Detection 4
The output closes when the output frequency is above the detection level set in L4-03. The terminal remains closed until the
output frequency or motor speed falls below L4-03 minus the setting of L4-04.
Status
Description
Open
Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03.
Closed
Output frequency or motor speed exceeded L4-03.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
4.8 Detailed iQpump Parameter Descriptions