Yaskawa iQpump Micro User Manual

Page 146

background image

L4-04

Frequency
Detection 4

ON

OFF

L4-03

Output Frequency

or Motor Speed

Figure 4.52 Frequency Detection 4 Example with Positive L3-04 Value

Setting 1A: During Reverse

A digital output set for “During reverse” closes when the drive is running the motor in the reverse direction.

Status

Description

Open

Motor is being driven in the forward direction or stopped.

Closed

Motor is being driven in reverse.

Output frequency

time

FWD Run command

REV Run command

During Reverse

OFF

ON

Figure 4.53 Reverse Direction Output Example Time Chart

Setting 1B: During Baseblock (N.C.)

The output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not

operate and no main circuit voltage is output.

Status

Description

Open

Baseblock is being executed.

Closed

Drive is not in a baseblock state.

Setting 1E: Restart Enabled

An output set for “Restart enabled” closes when the drive attempts to restart after a fault has occurred.
The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is

cleared and the drive has attempted to restart. If the drive cannot successfully restart within the number of attempts permitted

by L5-01, a fault will be triggered and the terminal set to 1E will open.

Setting 1F: Motor Overload Alarm (oL1)

The output closes when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection level.

Setting 20: Drive Overheat Pre-Alarm (oH)

The output closes when the drive heatsink temperature reaches the level specified by parameter L8-02. .

Setting 22: Mechanical Weakening Detection

The output closes when a mechanical weakening situation is detected.

4.8 Detailed iQpump Parameter Descriptions

146

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual