Simple duplex system application example – Yaskawa iQpump Micro User Manual

Page 115

background image

No.

Parameter Name

Setting Values

P9-27

Network Recovery

Default: 0

Range: 0 to 3

U9-02

Network Activity

No signal output available

U9-04

Running Queue Number

No signal output available

n

Simple Duplex System Application Example

A customer requires a duplex system with the following capabilities:
• Control the system pressure using two drives (no PLCs).
• Alternate drives everyday to even out the pump wear.
• Toggle switch for Run command.
• Each drive will have its own feedback transducer. Due to the shut-off valves, the network feedback should not be used as a

backup.

• Pump is at optimal running speed when at fixed speed of 54.0 Hz.
• Setpoint is 100 PSI, feedback scale is 145 PSI, start level is 80 PSI.

Drive A

15 HP

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

PRES

SURE FEED

BACK

A

R+

S+

S-

R-

A2

AC

+V

A1

SN

S1

PRESSURE FEEDBACK B

RUN

RUN

Drive B

15 HP

Figure 4.16 Simplified Wiring Diagram

Table 4.11 Related Parameters for Simple Duplex System Example

Description

Drive A

<1>

Drive B

<1>

Run Source: 1 (Terminals)

b1-02 = 1

b1-02 = 1

Node Address

H5-01 = 1

H5-01 = 2

Highest Node Address

P9-25 = 2

P9-25 = 2

Pump Mode: 3 (Network)

P1-01 = 3

P1-01 = 3

Feedback Source: 0 (Analog)

P9-02 = 0

P9-02 = 0

Lag Fixed Speed

P9-06 = 54.0 Hz

P9-06 = 54.0 Hz

Setpoint

U5-99 = 100 PSI

U5-99 = 100 PSI

Start Level

P1-04 = 80 PSI

P1-04 = 80 PSI

<1> All other multiplexing and alternation parameters are set to default settings.

Duplex System with Fine Tuning Application Example

The customer would like to solve a pump cycling problem. Currently the second drive runs for 10 to 20 seconds at minimum

speed then shuts off, letting the first drive run at maximum. This will then run the second drive again and the cycle will repeat.

The customer must also account for system losses when running both pumps by boosting the setpoint by 5 PSI. In the event

that the pressure exceeds 125 PSI, the second drive should de-stage if both drives are running. If the pressure exceeds 140

PSI, a high feedback fault should occur and stop the drive.
There are multiple methods to handle the pump cycling problem:
• Lower the lag fixed speed (P9-06)

4.7 iQpump Presets and Functions

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

115