B.4 d: References

Reference parameters are used to set the various frequency reference values during operation.

u

d1: Frequency Reference

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d1-01

(0280)

Frequency Reference 1 Reference 1

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-02

(0281)

Frequency Reference 2 Reference 2

Frequency reference when digital input "Multi-Step Speed

Reference 1" (H1-oo = 3) is on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-03

(0282)

Frequency Reference 3 Reference 3

Frequency reference when digital input "Multi-Step Speed

Reference 2” (H1-oo = 4) is on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-04

(0283)

Frequency Reference 4 Reference 4

Frequency reference when digital inputs "Multi-Step Speed

Reference 1, 2" (H1-oo = 3 and 4) are on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-05

(0284)

Frequency Reference 5 Reference 5

Frequency reference when digital input "Multi-Step Speed

Reference 3" (H1-oo = 5) is on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-06

(0285)

Frequency Reference 6 Reference 6

Frequency reference when digital inputs "Multi-Step Speed

Reference 1, 3 " (H1-oo = 3 and 5) are on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-07

(0286)

Frequency Reference 7 Reference 7

Frequency reference when digital inputs "Multi-Step Speed

Reference 2, 3" (H1-oo = 4 and 5) are on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-08

(0287)

Frequency Reference 8 Reference 8

Frequency reference when multi-function input "Multi-Step

speed reference 1, 2, 3" (H1-oo = 3, 4, 5) are on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-09

(0288)

Frequency Reference 9 Reference 9

Frequency reference when multi-function input "Multi-Step

Speed Reference 4" (H1-oo= 32) is on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-10

(028B) Frequency Reference 10 Reference 10

Frequency reference when digital input "Multi-Step Speed

Reference 1, 4" (H1-oo = 3 and 32) are on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-11

(028C) Frequency Reference 11 Reference 11

Frequency reference when digital inputs "Multi-Step Speed

Reference 2, 4" (H1-oo = 4 and 32) are on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-12

(028D) Frequency Reference 12 Reference 12

Frequency reference when digital inputs "Multi-Step Speed

Reference 1, 2, 4" (H1-oo = 3, 4, 32) are on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

d1-13

(028E) Frequency Reference 13 Reference 13

Frequency reference when digital inputs "Multi-Step Speed

Reference 3, 4" (H1-oo = 5 and 32) are on.

Default: 0.00 Hz

Min.: 0.00
Max.: 400.00

<1>

B.4 d: References